3-11. Connecting Input Power

2
Tools Needed:
Y Turn Off welding power source, and
check voltage on input capacitors
according to Section 8-1 before
proceeding.
Y Installation must meet all National
and Local Codes − have only qualified
persons make this installation.
Y Disconnect and lockout/tagout input
power
before
connecting
conductors from unit.
Y Make input power connections to the
welding power source first.
Y Always
connect
green/yellow conductor to supply
grounding terminal first, and never to
a line terminal.
1
Input Power Conductors (Customer
Supplied Cord)
Select size and length of conductors using
Section 3-10. Conductors must comply with
national, state, and local electrical codes. If
OM-217 751 Page 16
3
5
4
7
1
current transducer to ground terminal.
5/16 in
applicable, use lugs of proper amperage
capacity and correct hole size.
Welding Power Source Input Power
Connections
2
Strain Relief
Install strain relief of proper size for unit and
input conductors. Route conductors (cord)
through strain relief and tighten screws.
S Use large strain relief for input conductor
input
size 8 and larger.
S Use small strain relief with reducing
washers for input conductor size 10.
Connect input conductors as shown in
green
or
illustration.
Route green or green/yellow grounding
conductor through current transducer and
connect to welding power source grounding
terminal first. Then connect input conductors
L1, L2, and L3 to welding power source line
terminals.
Reinstall side panel onto welding power
source.
= GND/PE Earth Ground
8
3
L1
L2
6
L3
Route input power cable
through tubing inside unit.
Route ground conductor through
WARNING
ELECTRIC SHOCK can kill;
SIGNIFICANT DC VOLTAGE
exists after removal of
input power.
S Always wait 5 minutes after power
Is turned off before working on unit.
S Check input capacitor voltage, and
be sure it is near 0 before touching
any parts.
Read Owner's Manual.
Three-Phase Input Connection
803 823-A / Ref. 803 766-A / 218 005-A
Disconnect
Device
Input
Connections
3
Disconnect Device (switch shown in
the OFF position)
4
Green Or Green/Yellow Grounding
Conductor
5
Disconnect Device Grounding Terminal
6
Input Conductors (L1, L2 And L3)
7
Disconnect Device Line Terminals
Connect green or green/yellow grounding
conductor to disconnect device grounding
terminal first.
Connect input conductors L1, L2, and L3 to
disconnect device line terminals.
8
Over-Current Protection
Select type and size of over-current protec-
tion using Section 3-10 (fused disconnect
switch shown).
Close and secure door on disconnect device.
Remove lockout/tagout device, and place
switch in the On position.
Power