Chromalox RG-PK-1 Инструкции по установке

Просмотреть онлайн или скачать pdf Инструкции по установке для Кабели и разъемы Chromalox RG-PK-1. Chromalox RG-PK-1 2 страницы. Power connection kit

ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heating cable and
accessories. A qualified person must perform
installation and service of heating cable and
accessories. Heating cable must be effectively
grounded
in
Electrical Code. Failure to comply can result in
personal injury or property damage.
NOTE: All electrical wiring including GFCI (Ground Fault
Circuit Interrupters), must be done according to National
Electrical or local codes by a qualified person.
1. Slide the four (4) components of the nylon cable connector
onto the heating cable in the order shown.
2. Assemble the connector and tighten, leaving six inches of
cable extending through the connector.
3. Score the cable outer jacket 3-1/2" from the cable end.
Remove the jacket to expose the braid.
© 2010 Chromalox, Inc.
RG-PK-1 Power Connection Kit
accordance
with
3
4
6"
GENERAL
CAUTION: Do not damage the braid or the base cable insulation.
the
National
4. Pick the braid apart near the outer jacket and pull the cable
through the opening in the braid. Twist the braid into a pigtail.
1
2
5. Using standard electrical cutters, cut a 3/4" long notch out of
the cable, between the two conductor wires. Bare a 3/8" length
of each conductor by stripping off the outside insulation and
the inner black core material.
4
(Supersedes PJ478-1)
MARCH, 2004
3-1/2"
RG
PJ478-2
161-511930-002