2. Then go to setting mode 2.
Setting mode 2
CHECK
button
SET button
TIMER UP/
DOWN buttons
Setting procedure
● To enter the setting mode, press and hold the CHECK
button, SET button, and CANCEL button simultaneously for
4 seconds or longer.
● Press the TEMPERATURE UP and DOWN buttons to
change the parameter.
● During this mode, "SET DATA" is displayed, blinking. The
display shows the set outdoor unit address "System XX-YY"
(System XX = system address; YY = address at outdoor unit
sub-bus), parameter number, and the value (8 digits).
The value is displayed in 8 digits. The display changes
between the first 4 digits and the last 4 digits. When the first
4 digits are displayed, the top point of the colon is lit.
● Press the TIMER UP and DOWN buttons to change the
value. To confirm the changed value, press the SET button.
At this time, "SET DATA" display stops blinking and remains
lit.
● To exit setting mode, press the CHECK button. The remote
controller display returns to the normal display mode.
Required settings
● Once you entered the setting mode 2, use the TEMP. UP
and DOWN buttons to go to parameter 4B.
With the TIMER buttons, change the value to "000".
(Decrease maximum condensing temperature)
● Additionally, go in similar manner to parameters 35 and
36 and change each value to "+004". (Decrease maximum
condensing temperature)
● Then go to parameter E1 and change it to "-018". (Air curtain
in cooling mode goes in Thermostat Off status 2 minutes
after the blow out temperature is exceeded, in order to avoid
too much condensate occurrence)
■ ECO G series units
GF2
3-PIPE
U-16GF2E5, U-20GF2E5, U-25GF2E5
U-16GE2E5, U-20GE2E5, U-25GE2E5,
GE2
2-PIPE
U-30GE2E5
2-PIPE,
U-16GEP2E5, U-20GEP2E5,
GEP2
High Power
U-25GEP2E5
TEMP.
UP/DOWN
buttons
CANCEL button
Fig. 8-2
1. After finishing the addressing procedure (refer to the
outdoor unit test run service manual supplied with the
outdoor unit), note down the address of the air curtain unit
such as 1-1 or 2-18 etc. and go to the outdoor unit electrical
board.
Outdoor unit electrical board
Setting procedure
● Press the UP (S005) or DOWN (S006) key to scroll through
the menu items.
During and after menu item changes, the menu number
display appears for about 1 second (0.7 seconds), followed
by the letter display.
● To select a menu item, press the SET (S007) key during the
menu number display period.
● When the HOME (S004) key is pressed, the display will
always show "no00." (contents will not change during
setting).
● When no operations occur for 10 minutes in areas other than
item "no00.", then item "no00." will be displayed (contents
will not change during setting).
Required settings
● With the UP and DOWN buttons go to menu 6: "SEt in"
● Press the SET key, and then by using the UP and DOWN
buttons choose the previously noted address of the air
curtain.
Example: For address 1-1 you must choose "1." in the
display, for address 2-18 you must choose "18.".
● In the second position of the display you will see the
parameter number. By using the UP and DOWN buttons, go
to each of the following parameters, press the SET button,
then change with the UP and DOWN button the value and
press SET button again, then go to the next parameter:
"1." set to 1 (RAP valve present)
"6." set to 1 (air speed in Thermo Off does not change)
"L." set to 16 (blow-out temperature in cooling should not go
below +16 °C)
"n." set to 38 (optimum blow-out temperature in heating is
+38 °C)
● Then press the HOME button and with the UP and DOWN
buttons go to menu 5: "SEtout"
● Press the SET key and by UP and DOWN buttons go
to parameter "A0", press SET again and change this
value to 2, press SET again and finalize the setting by
pressing the HOME button. (Air curtain in cooling mode
goes in thermostat off status 2 minutes after the blow
out temperature is exceeded in order to avoid too much
condensate occurrence)
21
Fig. 8-3