SYSTEM COMPONENTS
Model
Description
IH357
Single gang ring for VM104 (mounts to
drywall) or IH358 (Steel City #52171).
IH358
Double bang box for IH357 Ring (Steel City
#52C14).
SS250
250 VA 16 VAC Transformer. One required
per control unit and power supply.
PK314A
Control unit (amplifier and power supply). One
required per system.
PK311
Power supply. See system layout section for
number of units required.
PK417
Dual entrance transfer relay. One required for
each additional entrance panel, maximum three
panels per system. See Figures 6 & 7 for wiring.
VM104
Video monitor—black & white.
VM320B
Camera panel—black & white.
PK320
Video distribution amplifier (4 outputs). See
system layout section for units required.
VM600B
Entrance panel—black & white camera.
CM Series
Button panels.
AM Series
Button panels.
EQUIPMENT LOCATION AND
HOUSING INSTALLATION
Entrance Panel (VM320B) Enclosure:
A. Do not locate the entrance panel in areas of extreme heat
or cold (where the operating temperature range of 0°C-
40°C might be exceeded), or where panel will be
exposed to moisture or adverse weather conditions.
B. Locate the entrance panel away from direct sunlight.
Provide sufficient light to illuminate the caller at night, by
installing a minimum of one 40 watt fluorescent bulb
above the entrance panel. For best picture quality, the
light source should be directed to illuminate the caller's
face.
C. The top of the housing should be located approximately
66" (1.7 m) above the finished floor surface, to place the
camera opening approximately 61" (1.5 m) above the
finished floor.
D. If a PO202I Post Office key door release panel is used, the
minimum panel size is 3 gang. For additional
buttons, consult the Entrance Panel Housing Chart (Fig-
ure 1).
Control Unit:
The Control Unit (PK314A Amplifier and Power Supply)
should be installed inside the entrance panel. If for some
reason the control unit must be installed away from the
entrance panel, observe notes regarding wiring, and locate
where the operating temperature of 0°C-40°C will not be
exceeded.
Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.
Transformer:
The transformer must be located in an accessible area near a
source of 117 VAC and away from extreme heat. The
transformer should be kept at least 3' (but preferably not
more than 50') away from the PK314A. Observe all local
electrical codes.
Video Monitor:
Locate the video monitor in an area where the operating
temperature does not exceed 0°C-40°C and the humidity is
not high. The top of the VM104 housing (IH357, IH358)
should be located approximately 66" (1.7 m) above the
finished floor. Refer to Figure 3 and to Wire Connections
and Equipment Installation, Video Monitor section, for
installation of IH357 ring or IH358 back box.
SYSTEM LAYOUT
A. Maximum number of VM104 monitors per PK314A is
50 units. Only one PK314A control unit is used per
system.
B. Each additional 20 VM104 monitors require a PK320
amplifier. (See Figure 8 for PK320 wiring and installa-
tion instructions.)
C. Each additional 80 VM104 monitors require a PK311
power supply and an SS250 transformer. (See Figure 8
for PK311 wiring and installation instructions.)
D. Up to three separate VM320B entrance panels may be
used per system, following the above guidelines for each
entrance panel used. (See Figures 6 and 7 for wiring
instructions.)
WIRING INSTRUCTIONS
Run wires according to Figure 4, in conjunction with the
following notes.
A. Each VM104 is supplied with an RG59U connector
board for RG59U cable.
B. The maximum number of VM104 monitors per riser is
20. The maximum length of each riser is 200'.
A PK320 video distribution amplifier must be added for
every additional 20 monitors (20 per riser) or 200' of
cable (see item E below).
C. Wire gauge sizes for common wires only are as follows:
+, -
Minimum 18 gauge for up to 50 monitors.
Minimum 16 gauge for up to 100 monitors.
1,2,3,4
Two twisted pair 22 gauge. Must be shielded
pairs if not in metal conduit.
CT
#18
Intercom communication common wires must be routed
away from fluorescent lights and AC lines. For
®
IL498 Tek-VIEW