Cells Per Unit
Voltage Per Unit
Optimal Operating
Temperature
Operating Temperature Range
(Storage)
Operating Temperature Range
(Discharging)
Operating Temperature Range
(Charging)
Float
Charge Voltage
Absorb or Equalize
Charge Voltage
Maximum Charge Current
Charging Temperature
Compensation Factor
Relative Humidity
Terminal
Terminal Torque
Weight
Dimension L x W x H
Warranty
Table 3
Discharge in Hours:
EnergyCell 200PLC
900-0227-01-00 Rev A
Table 2
2
Ampere-Hour Capacity to 1.75 Volts Per Cell at 25°C
1
2
104
120
Specifications
Specifications
EnergyCell 200PLC
6
12V
68°F to 86°F
(20°C to 30°C)
–4° to 104° F
(–20° to 40° C)
–40° to 149° F
(–40° to 65° C)
–5° to 140° F
(–15° to 60° C)
13.5 Vdc
14.1 Vdc
50 Adc
±5 mV / °C / cell
0% to ~95%,
non-condensing
T11
97.4 to 130.1 in-lb
(11 to 14.7 Nm)
~130 lb
(~59 kg)
22.0 × 4.92 × 12.6"
(559 × 125 × 320 mm)
6 years (global),
full replacement
3
4
5
8
132
140
145
160
12
20
24
48
168
178
182
191
100
200
19