Alarms
Alarms
Buzzer
Sounds
The buzzer stops after 20S.
Protections
Overload or Output Short Circuit Protection
Overload
Character
Continuance
Recover 3
times
If the overload or short circuit status still remains when the inverter
tries to recover for 3 times, you should reduce or clear the loads
and then restart the inverter manually. Load over than 250% will be
treated as output short circuit.
Overload or Short circuit, No Output
Over or Low input voltage, No Output
Over temperature, No Output
Inverter Fault, No Output
125%
150%
60S
10S
Space 5 seconds for the first time, 10 seconds
for the second time, and 15 seconds for the
Status
200%
3S
third time
8
>250%
230%
<
<0.2S
0.01S