Axxeron HESCH HE 5710 Руководство по эксплуатации - Страница 17

Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Контроллер Axxeron HESCH HE 5710. Axxeron HESCH HE 5710 19 страниц. Solenoid valve controller

Note!
The terminals V5 (+ and -) to V8 (+ and -) for HE 5711 only!
5.4

Inputs

The solenoid valve controller has two inputs: START and START CYCLE The inputs are
internally supplied with +24 V DC and are active when they are switched to (-) with a potential-
free contact.
5.5

Valves

Connection:
HE 5710 on terminals V1 (+ and -) to V4 (+ and -)
HE 5711 on terminals V1 (+ and -) to V8 (+ and -)
Valve type: 24 V DC, max. 1 A
Common potential: -
Switched output: +
The outputs are short-circuit-proof.
5.6

Commands

Permanent operation: connect the terminals START (+ and -).
Cycle operation:
HE 5710 / 5711 Operating Instructions
# 371814 | Version 1.4
connect the terminals START CYCLE (+ and -) (trigger signal).
17