Cisco ASR 920 series Руководство по установке - Страница 23
Просмотреть онлайн или скачать pdf Руководство по установке для Переключатель Cisco ASR 920 series. Cisco ASR 920 series 36 страниц. Aggregation services router
Также для Cisco ASR 920 series: Начало работы (6 страниц), Руководство по установке (42 страниц), Руководство по установке оборудования (46 страниц), Руководство (36 страниц)
Chapter 3
Installing the Cisco ASR 920 Series Router
Power Connection Guidelines
This section provides guidelines for connecting the Cisco ASR 920 Series Aggregation Services Router
power supplies to the site power source.
•
•
•
Never defeat the ground conductor or operate the equipment in the absence of a suitably installed
Warning
ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are
uncertain that suitable grounding is available. Statement 213
The plug-socket combination must be accessible at all times because it serves as the main
Warning
disconnecting device. Statement 1019
This product requires short-circuit (overcurrent) protection, to be provided as part of the building
Warning
installation. Install only in accordance with national and local wiring regulations. Statement 1045
Guidelines for DC-Powered Systems
Basic guidelines for DC-powered systems include the following:
•
•
•
•
•
•
•
Guidelines for AC-Powered Systems
Basic guidelines for AC-powered systems include the following:
•
•
•
OL-32751-01
Preventing Power Loss, page 3-24
Activating a DC Power Supply, page 3-24
Activating an AC Power Supply, page 3-24
Each chassis power supply should have its own dedicated input power source. The source must
comply with the safety extra-low voltage (SELV) requirements in the UL 60950, CSA 60950, EN
60950, and IEC 60950 standards.
The circuit must be protected by a dedicated two-pole circuit breaker. The circuit breaker should be
sized according to the power supply input rating and local or national code requirements.
The circuit breaker is considered the disconnect device and should be easily accessible.
The system ground is the power supply and chassis ground.
Do not connect the DC return wire to the system frame or to the system-grounding equipment.
Use the grounding lug to attach a wrist strap for ESD protection during servicing.
Ensure the DC return is grounded at the source side.
Each chassis power supply should have its own dedicated branch circuit.
The circuit breaker should be sized according to the power supply input rating and local or national
code requirements.
The AC power receptacles used to plug in the chassis must be the grounding type. The grounding
conductors that connect to the receptacles should connect to protective earth ground at the service
equipment.
Cisco ASR 920 Series Aggregation Services Router Hardware Installation Guide
Installing the Chassis Ground Connection
3-23