Также для Siemens SINAMICS G120P: Руководство по эксплуатации (26 страниц), Руководство по эксплуатации (34 страниц), Руководство по эксплуатации (24 страниц), Руководство по эксплуатации (22 страниц), Руководство по эксплуатации (26 страниц), Руководство по эксплуатации (22 страниц), Руководство по эксплуатации (22 страниц), Руководство (18 страниц), Руководство по эксплуатации (18 страниц)

Siemens SINAMICS G120P Руководство по эксплуатации
General
Risk of burns due to high surface temperature of the du/dt reactor
The surface temperature of the du/dt reactors may exceed 80 °C. You can get seriously
burnt when touching the surface.
• Mount the du/dt reactors so that they cannot be touched. If this is not possible, attach a
NOTICE
Damage to the Voltage Peak Limiter due to interchanged connections
The Voltage Peak Limiter will be damaged if the input and output connections are
interchanged.
• Connect the incoming cable from the DC link of the Power Module to DCPS, DCNS.
• Connect the outgoing cable to the du/dt reactor to 1U2, 1V2, 1W2.
NOTICE
Damage to the du/dt filter by using components that have not been released
When using components that have not been released, damage or malfunctions can occur
at the devices or the system itself.
• Only use du/dt filters that SIEMENS has approved for operation with SINAMICS.
NOTICE
Damage to the du/dt filter if it is not activated during commissioning
The du/dt filter may be damaged if it is not activated during commissioning.
• Activate the du/dt filter during commissioning via parameter p0230 = 2. The pulse
NOTICE
Damage to the du/dt filter if a motor is not connected
Du/dt filters which are operated without a motor being connected can be damaged or
destroyed.
• Never operate a du/dt filter connected to the Power Module without a connected motor.
Note
Cable lengths
Keep the connecting cables to the Power Module as short as possible (max. 5 m).
12
CAUTION
clearly visible and understandable warning notice at hazardous positions.
frequency will then be limited automatically to permissible values following this.
dV/dt filter plus Voltage Peak Limiter
Operating Instructions, 04/2014, A5E32847105B AB