Siemens SINAMICS GL150 Справочное руководство - Страница 28

Просмотреть онлайн или скачать pdf Справочное руководство для Промышленное оборудование Siemens SINAMICS GL150. Siemens SINAMICS GL150 44 страницы. Medium-voltage drive
Также для Siemens SINAMICS GL150: Справочное руководство (38 страниц)

Siemens SINAMICS GL150 Справочное руководство
Tests
3.2 Function test
Result
The test is passed if the alarm is displayed on the test station computer.
3.2.15

Group fault Power Stack Adapter

Fundamentals
The test reveals whether the drive switches off when a group fault is pending on the Power
Stack Adapter.
Test procedure
1. The auxiliary voltage is present.
2. The cable at digital input DI7 of the Power Stack Adapter is interrupted.
Result
The test is passed if the drive responds as described above.
3.2.16

DriveCLiQ connection

Fundamentals
In automatic configuration, the installed DriveCLiQ components are detected and displayed on
the test station computer.
Test procedure
1. The auxiliary voltage is present.
2. The DriveCLiQ connector is removed at any DriveCLiQ component.
Result
The test is passed if the drive responds as described.
3.2.17

PROFIBUS connection with the excitation unit

Fundamentals
The PROFIBUS connection between the excitation unit and the drive is tested.
28
If present, contactor =LCI.PA3-A21/A22 +PP1 is removed.
The fault is displayed on the test station computer. The drive switches itself off.
A fault is displayed on the test station computer. The drive switches itself off.
SINAMICS GL150 6SL3855 F03 F70 F76 F79 F98 E11
Reference Manual Rev.201902141423 GL150 wassergekühlt