Connecting

4.1

Connecting the LU180

4.1.1

Cable entry

1. Loosen lid and remove it.
2. Install cable gland or conduit.
3. Insert wires through gland or conduit and up through cable guide.
4. Connect wiring.
5. Replace lid and tighten it.
* Lid removed for clarity
Note
• To maintain IP and NEMA ratings, tighten the lid between 4 to 4.5 Nm.
• Ensure the cable gland is screwed in to the enclosure tightly and the cable is within the
specified clamping range (6.5 to 12 mm).
• User supplied cable glands must meet IP68/NEMA 6 ratings and be installed according to
the manufacturer's instructions.
14
Operating Instructions, 09/2021, A5E37100674-AB