Siemens TIASTAR Руководство по эксплуатации - Страница 18
Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Промышленное оборудование Siemens TIASTAR. Siemens TIASTAR 44 страницы. Motor control center
3.12 Incoming LIne Termination Arrangements -
Main Lugs
Top main lugs only can be moved from one section to another
in the field without drilling holes in bus or structure.
Horizontal lugs are available with 600A bus, 42,000A Sym. bus
bracing only.
Amp/Bracing (A/K)
600A/42K
600A/42K-65K
600A/85-100K
600A/42K*
600A/65K*
800A/42K-65K
800A/85K-100K
800A/42K-65K**
1200A/42K-100K
1200A/42K-65K**
1600A/42K-100K
2000A/42K-100K
2000A/42K-100K
* Space behind structure not available.
** Entire rear of structure not available.
. Optional lugs available. Contact factory for size and rating.
18
Incoming.
Location
Cable Size.
Top
Qty = 2
#4 - 350MCM CU/AL
Top
Qty = 2
#2 - 600MCM CU/AL
Top
Qty = 2
#2 - 600MCM CU/AL
Bottom
Qty = 2
#4 - 350MCM CU/AL
Bottom
Qty = 2
#4 - 350MCM CU/AL
Top
Qty = 2
#2 - 600MCM CU/AL
Top
Qty = 2
#2 - 600MCM CU/AL
Bottom
Qty = 2
#2 - 600MCM CU/AL
Top
Qty = 3
#2 - 600MCM CU/AL
Bottom
Qty = 3
#2 - 600MCM CU/AL
Top
Qty = 4
#2 - 600MCM CU/AL
Top
Qty = 6
#2 - 600MCM CU/AL
Bottom
Qty = 6
#2 - 600MCM CU/AL
NOTE: Special lugs such as Burndy crimp type can be accom-
modated. Contact factory for space requirements.
Fig. Ref
Wire Bending.
Next Page
Space.Dim.A
16
13
17
16
18
20
19
13
19
13
17
16
18
20
20
18
18
20
20
18
21
20
21
29
22
46
Total Assembly Required Unit
Height.Dim. B
Space.Dim. C
12
0
24
12
30
18
18
12
24
18
24
12
30
18
30
24
30
18
30
24
30
18
48
36
72
72
Siemens Energy & Automation, Inc.