Siemens ULTRAMAT 6F Руководство по технике безопасности - Страница 21

Просмотреть онлайн или скачать pdf Руководство по технике безопасности для Промышленное оборудование Siemens ULTRAMAT 6F. Siemens ULTRAMAT 6F 24 страницы. Gas analyzer for the determination of ir-absorbing gases
Также для Siemens ULTRAMAT 6F: Руководство по дополнительному оборудованию (20 страниц), Руководство по эксплуатации (49 страниц)

Siemens ULTRAMAT 6F Руководство по технике безопасности
Siemens AG

Glossary

Dangerous failure
Failure with the potential to bring the safety-instrumented system into a
dangerous or non-functional status
Low Demand Mode
The frequency of demands for operation made on a safety related system is
no greater than one per year and no greater than twice the proof-test
frequency;
Safety function
Defined function executed by a safety-instrumented system with the
objective of achieving or maintaining a safe system status taking into account
a defined dangerous occurrence.
Example:
Monitoring of user defined threshold values.
Safety Integrity Level
SIL
Safety-instrumented system
A safety-instrumented system excludes the safety functions that are required
to achieve or maintain a safe status in a system. It consists of a sensor, logic
unit/ control system and final controlling element.
Example:
A safety-instrumented system is made up of a pressure transmitter, a limit
signal sensor and a control valve.
SIL
The international standard IEC 61508 defines four discrete Safety Integrity
Levels (SIL) from SIL 1 to SIL 4. Each level corresponds to the probability
range for the failure of a safety function. The higher the SIL of the safety-
instrumented system, the higher the probability that the required safety
function will work.
The achievable SIL is determined by the following safety characteristics:
Average probability of dangerous failure of a safety function in case of
demand (PFD
)
AVG
Hardware fault tolerance (HFT)
Safe failure fraction (SFF)
19 of 19
SIL Safety Manual ULTRAMAT 6 Gas analyzers
A5E00729183-02