Siemens 17 Запасные части и руководство по эксплуатации - Страница 6
Просмотреть онлайн или скачать pdf Запасные части и руководство по эксплуатации для Контроллер Siemens 17. Siemens 17 6 страниц. Combination starters
Replacement Parts and Instruction Guide
Instruction Guide
Notes: Toggle on circuit breaker must
Circuit Breaker Assembly Instructions
1.
Remove the two screws that connect the handle link to the
pivot assembly.
2.
Use a 5/16 " wrench to remove the two 1/4-20 screws and
lock washers which secure the handle to the enclosure
flange. These screws are located on the underside of the
enclosure flange. Remove the old handle assembly from
the enclosure.
3.
Remove the lever assembly from the panel and replace it
with one provided. The mounting panel may need to be
removed to access the mounting screws.
Siemens Industry, Inc. 3617 Parkway Ln, Peachtree Corners, GA 30092 www.usa.siemens.com
Circuit Breaker Handle Replacement Diagram *
4.
Hardware has been provided to mount a new circuit
breaker if necessary.
5.
Install the new handle assembly onto the enclosure.
6.
Reinstall the two 1/4 -20 screws and lock washers.
Make sure the handle housing is sealed against the
enclosure flange as this prevents the entry of moisture.
7.
Reinstall the two screws that connect the handle link to the
pivot assembly.
8.
No handle adjustment is required.
9.
Verify that the handle mechanism turns 'ON' and 'OFF' the
circuit breaker.
10.
Manually trip the circuit breaker and verify that the handle
will reset the breaker.
11.
Verify that the door cannot be opened with the handle in
the 'ON' position.
* Diagram applies to size 3.5 or 4 starters with E or F frame breaker
E87010-A0137-T003-A4
6