Siemens 550-506 Руководство по установке - Страница 8
Просмотреть онлайн или скачать pdf Руководство по установке для Контроллер Siemens 550-506. Siemens 550-506 9 страниц. Ce compliant dual duct controller -two air velocity sensors -electronic output
Document Number 550-308
Installation Instructions
Rev. 1, July, 2001
CAUTION:
The controller's DOs control 24 Vac loads only. The maximum rating is 12 VA for each DO.
Use an interposing 220V 4-relay module for any of the following:
•
VA requirements higher than maximum
•
110 or 220 Vac
•
DC power
•
Separate transformers used to power the load.
NOTE: Refer to the unit wiring diagrams or consult with the local representative if terminations are
missing or are different.
24 V-AC
C H GND
C
H
E
24 V-AC
C H GND
C
H
E
Page 8 of 9
DO 1
DO 2
DO 3
DO 4
DO 5
DO 6
NO C
NO C
NO C
NO C
NO C
NO C
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Y1 G Y2
Y1 G Y2
CW
CCW
CW
CCW
COMMON
COMMON
COLD DUCT
HOT DUCT
DAMPER
DAMPER
ACTUATOR
ACTUATOR
ELECTRIC HEAT STAGE 1 (OPTIONAL); OR, SPARE DO
Figure 9. Point Wiring for Application 2269 with Electric Reheat.
DO 1
DO 2
DO 3
DO 4
DO 5
DO 6
NO C
NO C
NO C
NO C
NO C
NO C
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Y1 G Y2
Y1 G Y2
CW
CCW
CW
CCW
COMMON
COMMON
COLD DUCT
HOT DUCT
DAMPER
DAMPER
ACTUATOR
ACTUATOR
O
C
C
L
P
O
E
N
S
E
D
VALVE ACTUATOR
(OR SPARE DOs)
Figure 10. Point Wiring for Application 2269 with Hot Water Reheat.
DO 7
DI 3
DO 8
DI 2
NO C
NO C
AI 3
WALL SWITCH (OPTIONAL); OR,
SPARE DI (DRY CONTACT CLOSURE ONLY)
DUCT TEMPERATURE SENSOR
(100K
THERMISTOR) (OPTIONAL)
AVS 2 AUTOZERO MODULE (OPTIONAL); OR,
SPARE DO
AVS 1 AUTOZERO MODULE OR ELECTRIC HEAT
STAGE 3 (OPTIONAL); OR, SPARE DO
ELECTRIC HEAT STAGE 2 (OPTIONAL); OR, SPARE DO
DO 7
DI 3
DO 8
DI 2
NO C
NO C
AI 3
WALL SWITCH (OPTIONAL); OR,
SPARE DI (DRY CONTACT CLOSURE ONLY)
DUCT TEMPERATURE SENSOR
(100K
THERMISTOR) (OPTIONAL)
AVS 2 AUTOZERO MODULE (OPTIONAL); OR,
SPARE DO
AVS 1 AUTOZERO MODULE (OPTIONAL); OR,
SPARE DO
FLN TRUNK
BST
+ - S
RX
TX
RTS
+ - S
ROOM TEMPERATURE SENSOR
FLN TRUNK
+ - S
BST
RX
TX
RTS
+ - S
ROOM TEMPERATURE SENSOR
Siemens Building Technologies, Inc.