IP Controller N350E
Slipping off bus connection blocks (Figure 3)
The bus connection block (D2) is situated on the top of
-
the device (D1).
The bus connection block (D2) consists of two com-
-
ponents (D2.1 and D2.2) with four terminal contacts
each. Take care not to damage the two test sockets
(D2.3) by accidentally connecting them to the bus ca-
ble or with the screw-driver (e.g. when attempting to
unplug the bus connection block).
Carefully put the screw-driver to the wire-inserting slit
-
of the bus connection block's grey component and
pull the bus connection block (D2) from the device
(D1).
Slipping on bus connection blocks (Figure 3)
Slip the bus connection block onto the guide slot and
-
press the bus connection block (D2) down to the stop.
-
Connecting bus cables (Figure 3)
The bus connection block (D2) can be used with single
-
core conductors Ø 0,6 ... 0,8 mm.
Remove approx. 5 mm of insulation from the conduc-
-
tor (D2.4) and plug it into the bus connection block
(D2) (red = +, black = -).
Disconnecting bus cables (Figure 3)
Unplug the bus connection block (E1) and remove the
-
bus cable conductor (E1.4) while simultaneously wig-
gling it.
D1
D
D2
Figure 3: Connecting and disconnecting bus wires
Technical manual
Update: http://www.siemens.com/gamma
2.12.1.12/4
D2
D2.3
D2.1 D2.2
D2.4
D2
5 mm
D2
D2.4
N350E, 4 Seiten
© Siemens AG 2013
Subject to change without further notice
Slipping off / on auxiliary power connection block
Follow the instructions for the bus connection block
-
when slipping off/on the auxiliary power connection
block.
Battery change
Lift the battery case cover (A12) with a screw driver.
-
Remove the battery with the battery holder.
-
Separate the old battery carefully from the battery
-
holder to which it is glued.
Insert the new battery in the battery holder and insert
-
both into the battery case. Ensure correct polarity (+
symbol) to achieve correct function of the real-time
clock.
Close the battery case with the battery case cover
-
(A12).
Battery type: Lithium CR 1/2 AA
-
Dimension Diagram
Dimensions in mm
b
b = 4 SU
1 Standard unit (SU) = 18 mm
General Notes
· The operating instructions must be handed over to the
client.
· A faulty device shall be returned with a Return Good
Note for Service provided by the appropriate Siemens
sales office.
· If you have further questions concerning the product
please contact our technical support.
' +49 (911) 895-7222
7 +49 (911) 895-7223
Infrastructure & Cities Sector, Building Technologies
P.O. Box 10 09 53, D-93009 Regensburg
5WG1 350-1EB01
44
55
Siemens AG
Control Products and Systems