Siemens XC10 Series Операция - Страница 19

Просмотреть онлайн или скачать pdf Операция для Блок управления Siemens XC10 Series. Siemens XC10 Series 32 страницы. Extinguishing control unit

Siemens XC10 Series Операция
4.1

Operating access levels

Building Technologies
Fire Safety
XC10xx-A operation is organized in several operating access levels.
Operating access level 1
This level gives access to:
-
silence buzzer
-
led test
-
fault detailed display
-
alarm counter display (XC1003-A and XC1005-A only)
Operating access level 2
This operating access level gives access, after code input on keyboard (4 2 3 3 by
default or personalized) or by key (option), to the following controls:
-
silence buzzer
-
silence / re-sound sounders
-
automatic blocked / automatic and manual blocked
-
disable / enable
-
test of zones 1...4
-
reset
-
test of sounders, warning panels, RT-alarm and RT-fault
Operating access level 2 is automatically disabled after 4 minutes if no handling is
carried out for this period.
To enable operating access level 2, enter the default code « 4 2 3 3 » on the
keypad or insert the key into the lock and turn it 90° clockwise (to the right):
LED « Operating access » (10) lights up (fixed)
In order to again block operating access Level 2, turn the key to the starting
position and remove it from the lock:
LED « Operating access » (10) is no longer lit
-
Operating access level 2 is automatically disabled after 4 minutes if no
handling is carried out for this period.
-
Operating access level 2 can be turned back manually to level 1 by entering
the same code (default: 4 2 3 2), without having to wait 4 minutes
In normal operation, only the green LED « System on » (1) is lit up and only
operating access level 1 operations can be carried out. However, note that:
-
yellow LED « Manual blocked » (14) or « Automatic blocked » (16) or both can
be lit up (fixed)
-
yellow LED « Extinguishing blocked » (11) can be lit up (fixed)
Operation
19
A6V10257477_c_en_--
2012-06