ActronAir CL01-2G Руководство по установке - Страница 7
Просмотреть онлайн или скачать pdf Руководство по установке для Панель управления ActronAir CL01-2G. ActronAir CL01-2G 8 страниц. Control interface
Installation Guide
NOTE
The Control Value is determined by the following example:
Control Value calculation at Probe weight value of 50% :
Control Value = 50% Room Temp + 50% Wall Cont Temp
= (0.5 x 18.0) + (0.5 x 26.8)
= 9.0 + 13.4
= 22.4
O
C (Displayed on CL01-2 as INSIDE temperature when
Important Note For Split Ducted Tri-Capacity Models:
By default, the Return Air Temperature Sensor is connected to the Indoor Board. As an option, this can be wired to
the Outdoor Board which will require changing the sensor setting from INDOOR sensor to OUTDOOR sensor via
Thermoregulation Gfc2, as shown on the right.
Thermoregulation
Room Temperature
Use OUTDOOR sensor
After Hours SW & Temp
Probe weight value
Room Temp.
Wall Cont Temp.
Control Value
Installation Guide - CL01-2 Control Interface Insert
Document: 9590-3026 Ver. 2 220907
CL01-2 Control Interface
button is pressed)
Gfc2
Change setting from
INDOOR sensor to
50
o
18.0
c
OUTDOOR sensor
26.8
o
c
18.0
o
c
7