ActronAir MGW-CLDCS Руководство по эксплуатации - Страница 5

Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Шлюз ActronAir MGW-CLDCS. ActronAir MGW-CLDCS 12 страниц. Vrf cloud gateway

2 Operation Instructions

2.1 Gateway Hardware

MGW-CLDCS Gateway [hereinafter referred to as the "Gateway"] is used together with "Cloud
Service" to upload VRF unit data to the cloud server through the Gateway.
The model adapted are ECOFLEX ODU + 3rd generation IDU or ECOFLEX ODU + ECOFLEX IDU.
The Gateway supports one RS-485 bus and is capable of taking in 8 refrigerant systems (the
maximum IDU quantity is 64); Supports 1 DI port which is defined as an emergency stop interface;
Supports 1 LAN port used for Web page configuration.
12V
Port
12V 0V
12 V DC power supply
Connect the ODU XYE port (*1) and support 8 refrigerant systems (up to 64 IDUs).
Multiple refrigerant system access gateways (*2), with the X/Y/E ports on the ODU
X Y E
master unit of each refrigerant system connected to the X/Y/E ports of the Gateway
in serial.
A B E
Reserved
Dry contact for short circuit connection of DI1 and M when the Gateway will start
emergency shutdown logic.
D I1 M DI2
* This function will release the startup lock of the IDU. The emergency stop function
is described in detail in the following sections.
LAN
Data are uploaded to the cloud server over the LAN.
*1: The X port of the Gateway is connected to the X port of the ODU, and the Y port of the Gateway
is connected to the Y port of the ODU.
*2: When multiple refrigerant systems are connected, they need to use different addresses.
0V
X Y E
A B E
DI1 M DI2
LAN
Function
04