Actuator Systems TCR-40C Series Инструкции по использованию - Страница 6
Просмотреть онлайн или скачать pdf Инструкции по использованию для Контроллер Actuator Systems TCR-40C Series. Actuator Systems TCR-40C Series 7 страниц. Intelligent on/off actuator
TCR-40C-All
Series-Intelligent on/off actuator usage instructions
Mounting instructions
Diagram1(With bracket)
Diagram1 UPVC plastic ball valve+bracket assembly,Diagram2 3piece stainless steel ball valve assembly
Diagram3 3piece stainless steel 3way ball valve assembly
Installed valve technical requirements
Valve type
wafer butterfly valve
flange butterfly valve
metal ball valve
plastic ball valve
□
1.If the ball valve is out of operation for a long time, and the torque value of first on or off is the max torque
□
2. When installing direct mount model valve, the hole deep ≤30mm. It requires cutting if the output shaft is longer than 30mm.
□
3. Pls pay attention to the following items if you install the bracket and coupling by yourself:
The intensity of bracket should meet the using requirements: the bracket twisting extent ≤0.2mm in the process of on or off.
※
The parallelism of bracket ≤0.5mm.
※
When processing the shaft hole at both end of the coupling, it is necessary to ensure the accuracy and concentricity. The
※
purpose is to make sure the mechanical hysteresis ≤10°, otherwise it will cause the actuator unable to work.
□
4. Screw should be installed spring washer、flat washer, and we suggest you daub some glue cement around the screw in
case of screw loosening.
□
5. After installation, user should switch the valve on and off one time with handle device first.
sure it works well.
PART 2
6
User Manual
Diagram2(Direct mount)
Recommend install condition
actuator rate torque≥2times valve max torque
actuator rate torque≥1.7times valve max torque
actuator rate torque≥1.7times valve max torque
actuator rate torque≥1.5times valve max torque
Success comes from our persistent pursue of perfect details.
Excellence originates from our persistence of win-win philosophy.
Notice:
1.When assembly with valve,it's suggest to use spring washer add
※
flat washer in order to fasten the screw and nut.
2.It's recommend to use 704 silica gel or instant cement instead of
※
anaerobic adhesive and UV glue.
3. Pls keep the actuator housing away from organic solvents,such as:
※
kerosene,butanone ,tetrachlormethane etc.,or the housing will crack.
Diagram3(Direct mount)
Modifying the valve after make
ISO9001
ISO9001
®
特克
.com
Made in china Global service