Argo ADICS13DC Руководство по установке - Страница 12

Просмотреть онлайн или скачать pdf Руководство по установке для Кондиционер Argo ADICS13DC. Argo ADICS13DC 19 страниц. Split air conditioner system
Также для Argo ADICS13DC: Руководство по эксплуатации (15 страниц), Руководство по эксплуатации (17 страниц)

15 - PUMP DOWN (See Installation Instruction of Outdoor Unit)
EN
Pump down means collecting all refrigerant gas in the system back into the outdoor unit without losing gas. Pump down
is used when the unit is to be moved of before servicing the refrigerant circuit.
16 - TEST OF THE SYSTEM AND CONTROL OF THE AIR VOLUME TO THE
OUTLET GRILLES
The unit is prearranged to supply an external static pressure of about 5 mm. Too high resistances in the air distribution
system can cause an exceedingly small air volume to the outlet grilles.
This trouble can be solved by increasing the fan speed as follows:
Open the cover of the electrical junction box.
A
Take out JP2.
B
C
9
8
7
6
5
4
3
2
1
0
300
500
L = Low fan speed
M = Middle fan speed
H = High fan speed
HH = Very high fan speed
ADIA
L
M
H
HH
700
900
1100
With the contact JP2 open, the external static
pressure will increase to about 7 mm. Check static
pressure and air flow rate on the fan performance
graph.
9
8
7
6
5
4
3
2
1
0
1300
1500
3
m
/h
H:
Standard supplied unit. Available fan speeds: Low-Middle-High
(L - M - H). Max. static pressure: about 50 Pa
HH: JP2 disconnected. Available fan speeds: Middle-High-Very high
(M - H - HH). Max. static pressure: about 62 Pa.
12
ADIB-C
L
M
H
300
500
700
900
HH
1100
1300
1500
3
m
/h