Argo AWIBS19 Руководство по установке - Страница 12
Просмотреть онлайн или скачать pdf Руководство по установке для Кондиционер Argo AWIBS19. Argo AWIBS19 18 страниц. Split air conditioner system
13 - OUTDOOR/INDOOR UNIT REFRIGERANT CIRCUIT ADDRESS
EN
Indoor units that are part of a multisplit system must be properly configured to be able to communicate with the
outdoor unit over different channels (Indoor A, Indoor B, etc...) of the communication bus.
Each indoor unit address must correspond to the physical connection of the indoor unit to the outdoor unit refrigerant
circuit, i.e.:
Refrigerant Circuit A <--> Indoor Unit Address A
Refrigerant Circuit B <--> Indoor Unit Address B
...
There are three methods to set the address of an indoor unit:
(1) Dip-switch setting: the address is set by mean of a dip-switch located on the indoor unit pcb.
(2) Remote controller procedure: the address is set with the remote control via parameter P08.
Wired controller procedure: the address is set with the controller via parameter P8
(3) Automatic addressing procedure: the address is automatically set on every indoor unit of the system starting the
automatic addressing procedure via parameter P30.
(1) ADDRESS SETTING THROUGH DIP-SWITCHES (UP TO 4 INDOOR UNITS)
Disconnect the power
Check that the setting of switch SW1 (PCB) corresponds to the figure:
INDOOR UNIT A
SW1
1=off
2=off
INDOOR UNIT C
SW1
1=off
2=on
(PCB factory state)
PCB
INDOOR UNIT B
SW1
1=on
2=off
INDOOR UNIT D
SW1
1=on
2=on
12
PCB
PCB