Installing the Cisco ONS 15530
Table 2-2
Table 2-2
Specifications
AC input voltage
AC input line frequency
AC input current
Installing and Removing the Power Supplies
To install an AC or DC power supply, follow these steps:
Remove the power supply from its packaging.
Step 1
Grasp the power supply handle with one hand. Place your other hand underneath to support the bottom
Step 2
of the external power supply.
Place the power supply correctly at the bay opening.
Step 3
Carefully slide the power supply into the bay. Make sure that the power supply is installed completely
Step 4
and that the faceplate is flush with the chassis.
Secure the power supply installation by securing the captive installation screws at the top of the power
Step 5
supply.
To power on the chassis, see the
To remove an AC or DC power supply, follow these steps:
Unplug the power cord on an AC power supply or remove the negative, positive, and ground connections
Step 1
from the DC power supply.
Note
Unscrew the captive installation screws at the top of the power supply.
Step 2
Grasp the power supply handle with one hand and pull the power supply out of the bay. Place your other
Step 3
hand underneath to support the bottom of the external power supply.
OL-7706-01
lists the nominal and acceptable value ranges for source AC power.
Source AC Power Specifications
Nominal Value
100 to 240 VAC, single
phase
50/60 Hz
8 A @100 VAC
3.5 A @240 VAC
"Powering Up the Shelf" section on page
The ground connections should always be connected first and disconnected last.
Acceptable Range
90 to 255 VAC
47 to 63 Hz
—
2-31.
Cisco ONS 15530 Hardware Installation Guide