Argo SDIAS8DC Руководство по установке - Страница 15

Просмотреть онлайн или скачать pdf Руководство по установке для Кондиционер Argo SDIAS8DC. Argo SDIAS8DC 19 страниц. Split air conditioner system
Также для Argo SDIAS8DC: Руководство по эксплуатации (15 страниц), Руководство по эксплуатации (17 страниц)

(2) ADDRESS SETTING THROUGH REMOTE CONTROLLER WITH PARAMETER P08 (UP TO 8 INDOOR UNITS)
• Press the button
• Press the arrow
until you visualize 08.
• Press the button
0 (factory setting) at the bottom starts flashing.
• Press the arrow
to set the unit's number.
• Confirm with the button
• Press
to exit the menu.
If the signal is received, the indoor unit will emit 5 consecutive beeps. Make sure that the signal is received only by the
indoor unit you want to set
NOTES
(3) AUTOMATIC ADDRESSING PROCEDURE
System requirements:
Outdoor unit must have a recent firmware version that supports the automatic addressing procedure.
Indoor units must have a recent firmware version that supports the automatic addressing procedure
Dip-switch for communication address setting on the indoor unit (SW2) must be left to the factory default state, i.e. to
the OFF position.
Activation of automatic addressing procedure with the parameter P30=1
Power on the whole system.
Verify that there is no error on the indoor units, but the "E0" error (address not set - see Auto-diagnosis table).
Switch on the remote controller of any of the indoor units of the system and set the parameter P30=1
• Press the button
• Press the arrow
until you visualize 30.
• Press the button
again for a few seconds: the number 0 (factory setting) at the bottom starts flashing.
• Press the arrow
to set the number 1.
• Confirm with the button
• Press
to exit the menu.
If the signal is received, the indoor unit will emit 5 consecutive beeps.
After some seconds, every indoor unit will show the following LED combination to confirm that the automatic addressing
procedure has been activated.
From this moment until the end of the procedure the indoor units will not receive
anymore the signals from the remote controllers (infrared receiver is disabled).
Execution of automatic addressing procedure
Once the procedure has been activated, the system will run automatically to set
the address of every indoor unit. In this period, compressor and fan motor will be
activated.
Once activated, the procedure takes about 4-5 minutes per outdoor unit circuit to
be completed. This time doesn't depend on the number of indoor units actually
connected to the outdoor unit, but on the number of refrigerant circuits of the outdoor
unit.
End of automatic addressing procedure
When all the circuits have been tested and the address of every indoor unit has been set, the outdoor unit will stop and
every indoor unit will switch off (standby mode).
In any case (procedure successful or failed) the infrared receiver of every indoor unit will be re-activated.
If there is no error on the indoor units, the system is ready to be used.
If there is the error "E0" (Address not set - see Auto-diagnosis table) on any indoor unit, re-run the automatic addressing
procedure or manually set the address on that indoor unit with the dip-switch or with the remote controller.
for a few seconds.
again for a few seconds: the number
.
for a few seconds.
.
OPERATION
GREEN
15
1 UNIT A
5
UNIT E
2 UNIT B
6
UNIT F
3 UNIT C
7
UNIT G
4 UNIT D
8
UNIT H
STANDBY
TIMER
RED
BLUE
EN