Cisco C880 E7-8800 v4 Руководство по установке оборудования - Страница 7
Просмотреть онлайн или скачать pdf Руководство по установке оборудования для Сервер Cisco C880 E7-8800 v4. Cisco C880 E7-8800 v4 31 страница.
1.3
Installation Specifications
This section explains installation specification of each model.
1.3.1 Installation Specifications
Dimensions
Width
[mm (in.)]
Depth (*1)
Length
Mass [kg (lb)] (*2)
Conditions for air
Max. calorific
conditioner
value
[kJ/h (BTU/h)]
Displacement
[m3/min (ft
(*3)
Temperature
and Humidity
conditions (*4)
Noise [dB] (*7, *8)
Acoustic power level [B] (*8)
Permissible
Vibration [m/s
(gal)]
Permissible dust level [mg/m
Power supply
Input voltage and source resultant pulse number
conditions
Frequency and fluctuating Range
Max power
consumption /
apparent power
Power factor (*10)
Inrush current [A] [Rush hours] (*11)
Leak current [mA] (*12)
*1: Dimensions without protrusions
*2: Numeric value when each optional device is mounted for maximum number of options.
However, rail for mounting rack (5.7kg) and cable type are not included.
Mass as per the installation configuration can be calculated using formula as shown below.
Device mass = 77 + (9.6 * A) + (2.5 * B) + (1.8 * C) + (3.3 * D) [kg]
A = Number of mounted SB (Minimum 1 to Maximum 4)
B= Number of mounted IOU (Minimum 1 to Maximum 4)
C= Number of mounted PSU (Minimum 2 to Maximum 6)
D= Number of mounted DU (Minimum 0 to Maximum 2)
*3: There are cases when device is overloaded or when abnormality is detected, FAN rotates at high-speed
even if recommended environmental temperature is used.
TABLE 1.2 Installation Specifications
Items
Interruptible power source
High efficiency power supply (*13)
Recommended environmental
3
/min)]
temperature
Max.
At the time
Temperature [°C (°F)]]
of operation
Humidity [%RH]
Max wet bulb
temperature [°C (°F)]]
Downtime
Temperature [°C (°F)]]
(*6)
Humidity [%RH]
Max wet bulb
temperature [°C (°F)]]
At the time of operation (Including
2
standby)
Downtime (*9)
3
]
At the time
Interruptible power
of operation
source (*13)
High efficiency power
supply (*13)
Downtime
Cisco C880 Server
(E7-8800 v2 CPU)
445(17.52)
782(30.79)
438(17.25) 10U
143(315)
21,600(20,500)
20,900(19,800)
12(424)
28(989)
(*5)
20 to 80
29 (84.2)
0 to 50 (32 to 122)
8 to 80
29 (84.2)
60
7.8
4.0 (400) (Composite seismic wave)
10.0 (1000) (Composite seismic wave)
0.15
200 to 240 VAC±10 %
1φ
50/60 Hz + 2/-4%
6.00 kW/6.19 kVA
5.81 kW/5.99 kVA
0.084 kW
0.95 or more
20 or less
6.9 or less
4
Contents
Cisco C880 Server
(E7-8800 v3 and
E7-8800 v4 CPUs)
19,872(18,835)
19.224(18,221)
5.52 kW/5.69kVA
5.34 kW/5.51kVA