finder 19.6K Руководство - Страница 6

Просмотреть онлайн или скачать pdf Руководство для Контроллер finder 19.6K. finder 19.6K 17 страниц. Knx actuator

finder 19.6K Руководство

1.5 Detailed description of the communication objects

1.5.1 DPT_Channel X Set ON/OFF F (1.001 Switch o 7.001 Value_2_Ucount)

The DPT_Channel X
Set ON/OFF message is relayed to the device in order to define the output status of
the channel X. The status of the relay on the X Channel switches mutually depending by the value assigned to
the PAR_Contact Type parameter. Moreover, the channel switching depends on the channel function set by
the PAR_Function parameter.
1.5.1.1
Function Set On/Off example
When the PAR_Function parameter is set to
DPT_Channel X - Status message is sent on the bus with the value of the new status of the
channel, as well as the DPT_Channel X - Status Inverted message (not shown), which
represents the negation.
1.5.1.2
Function Stairs light switching example
When the PAR_Function
channel switches from the OFF to ON status on receipt of DPT_Channel X
message. The resulting switching of the relay turn on the lights. The light timer remains locked
until the DPT_Channel X Set ON/OFF = Off message is received.
After the release of the button (instant t0, t'0 and t''0) the device starts the light timer that will
expire after the interval indicated by the PAR_Stairs Light Time (s) parameter. If the button is
pressed when lights are ON, the timer is stopped and subsequent release of the button
involves reset of the light timer (e.g. instant t'0). At the end of the turn-on period the device
switches the channel relay to OFF state, turning off the lights and sends the DPT_Channel X -
Status = Off message. In the figure are not shown the DPT_Channel X - Status Inverted
messages that are sent as well from the device in correspondence with the status changing.
FINDER SpA
Ver. 2018
Set On/Off . At each switching the
Stairs light Each time the button is pressed, the
KNX Actuator 19.6K
Set ON/OFF = On
6