Acuity Brands sensorswitch SFR5 Инструкции по программированию - Страница 2

Просмотреть онлайн или скачать pdf Инструкции по программированию для Аксессуары Acuity Brands sensorswitch SFR5. Acuity Brands sensorswitch SFR5 2 страницы. Occupancy sensor

Acuity Brands sensorswitch SFR5 Инструкции по программированию
FUNCTION DEFINITIONS ___________________________________
2 OCCUPANCY TIME DELAY
The length of time an occupancy sensor will keep the lights on after it last detects
occupancy (assuming Minimum On Time, if engaged, has been met).
4 100 HOUR BURN-IN / AUTO SET-POINT
TEST MODE
Disables Minimum On Time and sets Occupancy Time Delay to 30 sec.
Mode will expire after 10 min or if function 4 is set back to Normal.
100 HOUR BURN-IN
Overrides relay on for first 100 hrs of powered operation (typically for lamp
seasoning). LED blinks continuously while mode is enabled.
10 MINIMUM ON TIME
The length of time required for lamps to be on in order to prevent all short cycling
that shortens lamp life. If occupancy time delay expires prior to minimum on time
being satisfied, the lamps will remain on until time has been met.
DETAILED FUNCTION TABLES _____________________________
2 = Time Delay
1 30 sec
2 2.5 min
3 5.0 min
4 = Test Mode / 100 hr Burn-In / Auto Set-Point
1 Normal*
1
Test Mode will disable Minimum On Time and set Occupancy Time Delay to 30 sec.
Mode will expire after 10 min or if function 4 is set back to Normal.
10 = Minimum On Time
1 0 min
2 15 min*
4 7.5 min
5 10.0 min*
6 12.5 min
2 Run 100 hr Burn-In
3 30 min
4 45 min
(
)
*DEFAULT SETTING
7 15.0 min
8 17.5 min
9 20.0 min
6 Test Mode
5 60 min
1