A-LEVEL DETAILED FUNCTION TABLES ___________________________________________
2 = Lumen Compensation
1
Disabled (n100)
2
Enabled (n80)
3 = Idle Time Until Dim
1
30 sec
3
5 min
5
10 min
2
2.5 min
4
7.5* min
6
12.5 min
5 = Switch Tracking Channel
1 - 16 (e.g., 1 = Channel 1*; 2 = Channel 2; etc.)
6 = Follow Photocell Mode
1
Disable*
2
Enabled (Neg) 3 Enabled (Pos/Neg)
7 = Secondary Zone Dimming Offset
1 -100%
5 -60%
9
-20%
13 20%
2 -90%
6 -50%
10 -10%
14 30%
3 -80%
7 -40%
11 0% *
15 40%
4 -70%
8 -30%
12 10%
16 50%
8 = WallPod Dimming Adjustments
1 Permanent*
2
Temporary
9 = Restore Factory Defaults
1 Maintain Current*
2
Restore Defaults
19 = Dimming Rate
1 5 min
2 15 sec
3
4 2 sec
5 sec*
23 = Occupied Bright Level
1 1%
3 20%
5 40% 7 60% 9
80% 11
2 10%
4 30%
6 50% 8 70% 10 90%
24 = Unoccupied Dim Level
1 1%*
3
20%
5 40%
7 60% 9
2 10%
4
30%
6 50%
8 70% 10
B-LEVEL PROGRAMMING INSTRUCTIONS ______________________________
PLEASE READ ALL 4 STEPS BEFORE PROGRAMMING
1.
Enter B-Level programming mode by holding down button until status LED flashes rapidly, release, hold
down until rapid flash again, release, then immediately enter programming function as described in
step 2.
2.
Enter a programming function by pressing button the number of times as the desired function number
from the B-Level Detailed Function Tables below (e.g., press twice for function 2, Semi-
Auto Grace Period).
3.
Staus LED will flash back the selected function's current setting (e.g., 3 flashes for 15 sec). To change
setting, proceed to step 3 before flash back sequence repeats 3 times. To exit the current function or to
change to a different function, wait for sequence to repeat 3 times and return to step 1.
4.
Press button the number of times indicated in the particular function's detailed table for the new
desired setting (e.g., press 1 time for 0 sec). As confirmation of setting change, status LED flashes back
the new setting 3 times before exiting.  
INSTALLATION INSTRUCTIONS
• Mount through a ½" knockout in any junction box or luminaire. Secure with lock nut.
• Following above wiring diagram, connect wires to line voltage feed(s), neutral(s),
and load.
• Connect low voltage violet and gray dimming wires to 0-10 VDC driver leads and
green wire to an approved ground connection. Note wires have 600V rated insula-
tion.
• Interconnect unit (via RJ-45 ports) with other nLight devices in lighting zone using
CAT-5e cables.
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2014-2015 Acuity Brands Lighting, Inc. All rights reserved. August 24, 2015 10:57 AM
7
15 min
9
20 min
8
17.5 min
17 60%
21 100%
18 70%
19 80%
20 90%
3
Photocell Temp. Override
5
Instant
100%*
80% 11
100%
90%
*
Indicates Factory Default
NOTE:
For information on additional advanced settings, including resetting unit to factory
defaults, contact:
Technical Support: 1.800.535.2465
B-LEVEL DETAILED FUNCTION TABLES ___________________________
1 = Name Unit w/ Number
1 1
3 3
5
5
2 2
4 4
6
6
2 = Manual On (Semi-Auto) Grace Period
1 0 sec
3 15 sec*
3 = Predictive Exit Time
1 5 sec
3 7 sec
5
9 sec
2 6 sec
4 8 sec
6
10 sec*
4 = Predictive Grace Time
1 0 sec
3 10 sec
5
30 sec
2 5 sec*
4 20 sec
6
40 sec
11 = Occupancy Tracking
1 Disable
2 Enable*
12 = Occupancy Tracking Channel
1 - 16 (e.g., 1 = Channel 1*; 2 = Channel 2; etc.)
13 = Photocell Tracking
1 Disable
2 Enable*
14 = Photocell Tracking Channel
1 - 16 (e.g., 1 = Channel 1*; 2 = Channel 2; etc.)
15 = Switch Tracking
1 Disable
2 Enable*
17 = Forced Override
1 Disabled (not forced)*
2
Override On
18 = Special Operating Mode
1 Normal*
5
Predictive Off
2 Manual On
6
Manual to Override On
3 Auto to Override On
7
Manual to Normal
4 Manual to Full Auto
22 = Maintain Dim Level When Vacant
1 No*
2 Yes
23 = Special Switch Tracking Mode
1 Disable*
2 Ignore Offs
3 Ignore Ons
29 = Occupancy Expiration of Manual Off
1 Disabled* 2 Enabled
30 = Timed Expiration of Manual Off
1 Disabled* 2 Enabled
31 = High End Trim**
1 0.7V
3 2V
5 4V
7 6V
9 8V 11 10V
2 1V
4 3V
6 5V
8 7V 10 9V
32 = Low End Trim**
1 0.7V
3 2V
5 4V
7 6V
9 8V 11 10V
2 1V
4 3V
6 5V
8 7V 10 9V
*
Indicates factory default unless dependent on model number.
**
Setting precision of 0.1V is available via SensorView. Device status LED blinks out current value
rounded to nearest selection above.
BUTTON
RJ-45 PORTS
LED
7
9
7
9
8
8
10 Unassigned*
7
15 sec
9
30 sec
8
20 sec
7
50 sec
8
60 sec
3
Override Off
4 Ignore Ons & Offs
nPS 80 EZ