bits in a word, usually setting them all to 1 (TRUE) or 0 (FALSE). The firmware uses the
defined bits in the control words to perform important functions. Undoing the good work of
the firmware with your AP program is bound to cause trouble.
This means that, in many cases, the last block you will use in your AP program will be a
BSet block. Here is an example:
In this example, the block is toggling bit 11 of the MainCtrlWord (7.01) according to the
state of 84.09.0, leaving the other MainCtrlWord bits as they were before. The modified
copy of the MainCtrlWord is written to parameter 84.15. To complete this process, the
output must be set as follows:
This will direct the program to write the value of block 2 output (84.15) to parameter 701
MainCtrlWord (7.01). This all happens very quickly. The result will be that the value of bit
11 while change, but the other bits will remain intact.
For additional information
See the DCS800 firmware manual:
•
Page 67 – 75
•
Page 76 – 98
DCS800 Firmware manual supplement for North America (rev. 2.60, 2.70) Rev. b
Adaptive Program Instructions
Adaptive Program Function Blocks
15