Toshiba BMS-IFBN640TLE Руководство по установке - Страница 10
Просмотреть онлайн или скачать pdf Руководство по установке для Кондиционер Toshiba BMS-IFBN640TLE. Toshiba BMS-IFBN640TLE 14 страниц.

BN interface
3
Settings
3-1. Switch setting
SW300
Not used
SW301
Test switch
Set all bits to "OFF".
SW302
Test button
Not used during normal operation.
SW100
TCC-LINK terminator resistor setting switch
Set the TCC-LINK terminator resistor on the air conditioner side. Set SW100 to "OFF".
SW700
Shutdown function / air-conditioning search mode function button
Use this button to stop BACnet process and network process of the BN interface or to start up in the air-conditioning
search mode. Note that button operation changes depending on how long it is depressed.
Time duration button is depressed
Less than 4 seconds
4 seconds or more
10
-EN
Operation
Stop BACnet process and network process of the BN interface.
Starts air-conditioning in the air-conditioning search mode.
Use the air-conditioning search mode to set up equipment data in the indoor
unit.
Installation Manual