Safety Relay
Operating Instructions
Read and understand these instructions before installing,
operating, or maintaining the equipment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before working
on this device.
CAUTION
Reliable functioning of the equipment is only ensured with certified compo-
nents.
The safety relay must be installed in switchgear cubicles complying
with degree of protection IP32, IP43 or IP54, depending on the prevailing
environmental conditions.
IMPORTANT NOTICE
The products described herein are designed to be components of a customized
machinery safety-oriented control system. A complete safety-oriented system
may include safety sensors, evaluators, actuators and signaling components. It
is the responsibility of each company to conduct its own evalution of the effec-
tiveness of the safety system by trained individuals. ABB AG, its subsidiaries
and affiliates (collectively "ABB") are not in a position to evaluate all of the cha-
racteristics of a given system or product or machine not designed by ABB.
ABB accepts no liability for any recommendation that may be implied or stated
herein. The warranty contained in the contract of sale by ABB is the sole war-
ranty of ABB. Any statements contained herein do not create new warranties or
modify existing ones.
Application
The C6702 safety relay can be used in EMERGENCY STOP devices according to
DIN EN / IEC 60947-5-5 and in safety circuits according to
DIN EN / IEC 60204-1, e.g. in movable guards and protective doors or in non-
contact protective devices in accordance with DIN EN / IEC 61496-1 , electrical
equipment for furnaces in accordance with DIN EN 50156-1 and automatic firing
systems for gas burners in accordance with DIN EN 298 . Depending on the
external circuit, max. Performance Level PL e / Cat. 4 according to
DIN EN ISO 13849-1 and/or SIL 3 according to IEC 62061 can be achieved. The
user must carry out an evaluation of the overall systems.
Functional description and instructions for connection
The C6702 solid-state safety relay has one safe solid-state output and one time-
delayed safe solid-state output. Three LEDs indicate the operating state and the
function.
When the device is put into operation it runs through a self-test to test the
correct functioning of the internal electronics. All internal circuit components
are monitored for faults cyclically during operation.
Connect the EMERGENCY STOP button and/or the position switches or light
arrays to terminals Y11, Y12 and Y21, Y22. Connect the ON button in series with
the NC contacts of the external actuators to the supply voltage L+ (24 V DC) and
to terminal Y34. Connect cascading input 1 either via a safe output or directly to
the supply voltage L+ (24 V DC).
External actuators or loads can be switched via safe outputs 14, 24. It must be
ensured that the actuators or loads and the C6702 electronic safety relay have
the same frame potential. Paralleling outputs 14 and 24 to increase the load cur-
rent is not permissible.
If electronic sensors (light-array monitoring, etc.) are used, and in single-channel
operation, Y35 must be connected to L+ (24 V DC). For autostart operation, Y32
must be connected directly to L+ (24 V DC) and Y34 must be connected to it via
NC contacts of the external actuators.
Use a power pack to IEC 60536 safety class III (SELV or PELV)
for power supply!
Terminal
Operating
A1
assignments
voltage
A2
Sensors Y11, Y12
Y21, Y22
Y35
Y32
Y34
Input
1
Outputs
14
28
2
L+
M
Channel 1 EMERGENCY STOP or position switch
Channel 2 EMERGENCY STOP or position switch
With / without cross-circuit detection
Autostart
ON button, feedback circuit
Cascading input
Safe solid-state output
Safe solid-state output, time-delayed
Order No.: 2CDC 113 025 M9701
2
Cable lengths for 2 x 1.5 mm
max. 2000 m (total cable length for sensors)
Figures
Fig. I/Ia: Dimension drawings (dimensions in mm) / Terminal designation
Fig. II: Installation / Connection
Fig. IIIa: Safety data
Fig. IIIb: Application data
Fig. IV: Internal circuit:
¿
power pack,
Fig. V: Protective-door monitoring, two-channel, autostart;
with voltage-operated e.l.c.b. and delayed disconnection, stop
Fig. VI: EMERGENCY STOP, single-channel, monitored start with additional
ON button; with voltage-operated e.l.c.b. and delayed disconnection,
stop
Fig. VII: EMERGENCY STOP, two-channel, monitored start with additional ON
button; with voltage-operated e.l.c.b. and delayed disconnection
Fig. VIII: EMERGENCY STOP, two-channel, monitored start with additional
ON button and protective-door monitoring, two-channel, autostart
Fig. IX: Light-array monitoring, two-channel, autostart
Fig. X: Safety mat, two-channel, autostart
Operating states
LEDs
Operation
PS
POWER
RUN
FAULT
ON
4)
flashes
on startup self-test approx. 7 sec.
Faults
• Defect in electronics
• Change in terminal assignment
flashes
during operation
• Short-circuit to 24V
No supply voltage
Technical data
Permissible ambient temperature T
u
Operation / storage
Degree of protection to DIN EN / IEC 60529 IP40, IP20 at terminals
Rated insulation voltage
Rated impulse withstand voltage
Rated control supply voltage
Rated power
Operating range
Shock resistance (half-sine) as per
DIN EN / IEC 60068
Weight
Recovery time after EMERGENCY STOP
Recovery time after power failure
Release time after EMERGENCY STOP
Pickup time
Short-circuit protection
3)
Dark time
Start signal Y34
PFH / SFF (%)
MTTR / T1
Utilization category
Rated operational
voltage
as per IEC 60947-5-1
DC-13
24 V
1)
Sensor circuits open; Cross-circuit between the sensors; Short-circuit of sensors to frame
2)
only when using circuit variant with "cross-circuit detection"
3)
Safe outputs disconnected for test purposes; sufficiently slow actuators are not
affected.
4)
Delay time running
For further data and accessories see Catalog.
C6702
DIN EN / IEC 60947-5-1
English
À
sensors,
Á
Output 1,
Â
Output 2
EMERGENCY
ON button
Outputs
STOP
not activated was activated on
1)
activated
not activated
off
not activated not activated
off
activated
not activated
off/on
off
2)
–25 to +60 °C / –40 to +80 °C
50 V
500 V
24 V DC
1.3 W
0.9 to 1.15 x U
s
8 g / 10 ms
150 g
min. 200 ms
7 s
30ms/0.05 to 3s or 0.5 to 30s or 5 to 300s
max. 40 ms
no fusing necessary!
<1 ms
pulse (min.200 ms / max. 5 s)
–11
5,358x10
/ 99,35 %
8 h / 10 Years
Rated operational current
per output
1.5 A