1 = report the CR123A battery level.
0x65 (101)
To set what unsolicited report would be sent to the Lifeline group.
0 = Send Nothing.
1 = Battery Report.
2 = Multilevel sensor report for temperature.
3 = Battery Report and Multilevel sensor report for temperature.
0x6F (111)
Set the interval time for sending the unsolicited report that configured
by parameter 0x65. (Valid values 0x05-0x28DE80)
Note:
1.
The unit of interval time is second if USB power.
2.
If battery power, the minimum interval time is equal to Wake Up
interval set by the Wake Up CC.
0x87 (135)
To set which sensor report can be sent when the water leak event is
triggered and if the receiving device is a non-multichannel device.
0 = Send nothing.
1 = Send notification report to association group 1.
2 = Send configuration 0x88 report to association group 2.
3 = Send notification report to association group 1 and Send
configuration 0x88 report to association group 2.
0x88 (136)
When the parameter 0x87 is set to 2 or 3, it can get the sensor probes'
status through this configuration value.
If Bit 0 = 0, which means absence of water is triggered by probe 1.
If Bit 0 = 1, which means presence of water is triggered by probe 1.
If Bit 1 = 0, which means absence of water is triggered by probe 2.
If Bit 1 = 1, which means presence of water is triggered by probe 2.
Bit 2-7 = reserved.
Note:
This parameter is a Get- only parameter.
0xC9 (201)
Temperature calibration (the available value range is [-128,127] or [-
12.8 ,
12.7 ]).
Note:
1.
High byte is the calibration value. Low byte is the unit
(0x00=Celsius, 0x01=Fahrenheit)
2.
The calibration value (high byte) contains one decimal point. E.g.
if the value is set to 20 (0x1400), the calibration value is 2.0
(EU/AU version) or if the value is set to 20 (0x1401), the calibration
value is 2.0
3.
The calibration value (high byte) = standard value - measure
value.
E.g. If measure value =25.3
the calibration value= 23.2
If the measure value =30.1
calibration value= 33.2
0xFC (252)
Enable/disable Configuration Locked.
0 = Disable.
1 = Enable.
0xFF (255)
Value=0x55555555
( US version)
and the standard value = 23.2
- 25.3
and the standard value = 33.2
- 30.1
= 3.1
D efault=1
S ize=4
= -2.1
(0xEB).
, so the
(0x1F).
Page 11
3
3600
1
_
US version: 0x0001.
Other versions:
0x0000.
, so
0
N/A
1
4
1
1
2
1
4