Special provisions for mobile homes:
Exhaust vent must be securely fastened to a noncombustible
portion of mobile home and must not terminate beneath the
mobile home. Terminate exhaust vent outside.
Moblie Home Exhaust installation
Determine vent path:
Select route that will provide straightest and most direct
■
path outdoors.
Plan installation to use fewest number of elbows and turns.
■
When using elbows or making turns, allow as much room
■
as possible.
Bend vent gradually to avoid kinking.
■
Use as few 90° turns as possible.
■
Determine vent length and elbows needed for best
drying performance:
Use following Vent System Chart to determine type of vent
■
material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specified
in Vent System Chart. Exhaust systems longer than those
specified will:
Shorten life of dryer.
■
Reduce performance, resulting in longer drying times
■
and increased energy usage.
The Vent System Charts provide venting requirements that
will help achieve best drying performance.
Vent System Chart
Number of
Type
90° turns
of vent
or elbows
0
Rigid metal
1
Rigid metal
2
Rigid metal
3
Rigid metal
4
Rigid metal
NOTE: Bottom exhaust installations have a 90° turn inside the
dryer. To determine maximum exhaust length, add one 90° turn
to the charts.
18
Box/louvered
Angled
hoods
hoods
58 ft. (17.7 m)
64 ft. (20 m)
54 ft. (16.5 m)
48 ft. (14.6 m)
44 ft. (13.4 m)
38 ft. (11.6 m)
35 ft. (10.7 m)
29 ft. (8.8 m)
27 ft. (8.2 m)
21 ft. (6.4 m)
INSTALL VENT SYSTEM
1.
Install exhaust hood
Install exhaust hood and use caulking compound to seal
exterior wall opening around exhaust hood.
2.
Connect vent to exhaust hood
Vent must fit over the exhaust hood. Secure vent to exhaust
hood with 4" (102 mm) clamp. Run vent to dryer location
using straightest path possible. Avoid 90° turns. Use clamps
to seal all joints. Do not use duct tape, screws, or other
fastening devices that extend into interior of vent to secure
vent, because they can catch lint.
12" min.
(305 mm)
12" min.
(305 mm)