17
Note: After logging the device on to the system there may be two faults:- 1
fault is processor reset. 2
clear by stabilising the dome sounder, as explained in section 3, then press the
silence and reset buttons to clear the faults). The tamper fault will only appear
when switch 1 (Tamper Disable Switch) is set to the "Off" position, thus
enabling the tamper feature, as explained in Section 3.
18

2. Sounder volume

The dome's sounder volume can be adjusted using the switches as shown below in
Figure 2.
The switch settings for the volume are dispatched as HIGH volume, with switches 3 & 4
both in the "On" position.
Switch
settings
Sounder switches are exposed when removing the AA battery as shown below in Figure
3.
©2015 EMS Security Group Ltd. All rights reserved.
Press the "YES" key twice and the screen will now
display:
Press the "NO" key three times and the screen
will now display:
nd
fault is the Tamper. (Make sure the device tamper is
After the faults have been cleared, turn the
control key to the "OFF" position and the screen
will display:
High
3 On, 4 Off
HIGH
Medium
(Default)
3 & 4 On
3 Off, 4 On
Figure 2
Figure 3
5
| Slot is
>Logon is DISABLED<
| /\/\/\/\/\/\/\/\/\/\ |
01 FAULT
Default Device 125
ZONE 01 DEVICE 125
Status Normal
Date
Low
3 & 4 Off
TSD240 Iss 3 25/06/15 AJM
:IN USE |
TOT 02
st
Time