Programming
8
The FP-08451 Control Panel provides several programming options,
allowing it to be adapted to site conditions. The 2-way DIP switches
inside the panel next to the terminal block allow one of 4 modes to
be selected. To access the DIP switches, open the panel enclosure.
Switch 1
OFF
ON
Note: All programmed settings should be recorded in the logbook.
Note: If a Discharge Delay Module (P/N FP-08850) is installed, panel must be programmed for
extended discharge.
Control Panel Indicators & Operation
9
LED Indicators
9.1
The FP-08451 Control Panel uses LED indicators to notify the
operator of the condition of the control panel and each of the
monitored circuits.
following:
Circuit
Power
Circuit 1 Alarm
Circuit 2 Alarm
Fault
Isolated
Discharging
Agent Released
Isolate Function
9.2
To isolate the control panel, press and hold Mode Switch 1 until a 1 beep is heard and the
"Isolated" LED is illuminated. To restore the control panel to normal operation, press Mode
Switch 1 and ensure the "Isolated" LED turns off.
Isolating disables automatic activation. Manual Activation will remain operational.
When isolated, the control panel continues to monitor for alarm and fault, and show the alarm
and fault indications, but will not operate the siren and the automatic discharge.
Fire Detection and Activation System
Mode
Standard Discharge
Power Applied for 2
seconds
DEFAULT
Extended Discharge
Power applied for 240
seconds
If an LED is illuminated, it indicates the
LED
Power supply is available
System is in alarm condition
System is in alarm condition
System is in fault condition and needs servcing
System has been isolated using buttons on
panel
System has initiated activation sequence
Agent has been released and needs servcing
Switch 2
OFF
Condition
Model 08451
Mode
Manual Discharge
Detectors operate
siren/strobe only
Automatic Discharge
Detection on Circuit 1
ON
Alarm will discharge
system
DEFAULT
Rev 3.1
When
Page | 12