FirePro FP-08944-2 Краткое руководство по эксплуатации - Страница 5
Просмотреть онлайн или скачать pdf Краткое руководство по эксплуатации для Система безопасности FirePro FP-08944-2. FirePro FP-08944-2 8 страниц. Combined siren output module, fire system with multiple control panels
Operation
6
When any of the connected control panels enter an alarm condition, the siren/strobe will operate.
Once initiated, the siren/strobe will continue to operate until the control panel in alarm is silenced,
by pressing the mode switch (see FP-08450 Product Manual).
If multiple control panels are in alarm, the siren/strobe will continue to operate until all effected
control panels are silenced.
Commissioning
7
Commissioning should be performed when the fire control panel is not in an alarm/fault condition.
Note: No personnel should be in the risk area until the fire system is fully isolated.
Note: Where shutdown relays have been installed, all personnel should be made aware equipment
will not be operable until testing is completed.
1. Isolate and disconnect the any installed FirePro aerosol generators. This should generate a fault
on the fire control panel. Connect a FirePro FP-08800 Universal Test Lamp.
2. Put each of the connected control panels into alarm, by pressing and holding the buttons on the
fire control panel or through the detection circuits.
3. Ensure that any sirens or strobes connected to the system are operational and operate when
each of the connected panels is in an alarm condition.
4. Test the silence function is operable by pressing the Mode button on each control panel.
5. Test fault monitoring by disconnecting the plugs to each of the connected control panels and to
the siren/strobe.
6. Disconnect the FirePro FP-08800 Universal Test Lamp and reconnect all installed FirePro aerosol
generators.
Servicing and Maintenance
8
Inspection and servicing of the installed fire system should occur in accordance with the relevant
Australian Standards. This should include a visual inspection of the enclosure to ensure the seals
are intact.
Operation of any installed sirens/strobes and connected relays should be tested as outlined in (7)
Commissioning.
Combined Siren Output Module
Fire System with Multiple Control Panels
Model FP-08944
Rev 2.0
Page | 5