FIRETRACE Direct Systems Руководство по эксплуатации

System Overview.

The Fixed Firetrace® system is a simple self-actuating device that is designed to suppress fires
within an identified risk area.
The cylinder is not intended for portable use.
The system works by using pressurised Firetrace® linear detection tubing that is installed
throughout the risk area. This tubing is heat sensitive and when subjected to a temperature
above 120 Degrees centigrade, or when touched by flame, the Firetrace® tubing will rupture
and form a diffuser.
Tube burst forming diffuser
The FE-36 extinguishant is then deployed via this diffuser directly into the heart of the fire.
The Firetrace® system requires no external power source or separate detectors and owing to
its simple design ensures that all of the extinguishant is always deployed in the risk area.
The system can be fitted with a volt free single pressure switch (FT0124) or volt free twin
pressure switch (FT0124/T75) which, when connected to the cylinder, not only provides
constant monitoring of the system but can also send a signal to indicate a discharge via a Self
contained Alarm Sounder (FT0178).
It is important that both the cylinder & Firetrace® tubing are correctly installed and that the
system is subjected to a regular maintenance regime in line with BS5306-3 by a competent
engineer.
FT0178 Self-Contained Alarm Sounder