CALEFFI 152651 Краткое руководство по эксплуатации
Просмотреть онлайн или скачать pdf Краткое руководство по эксплуатации для Контроллер CALEFFI 152651. CALEFFI 152651 8 страниц. Temperature regulating unit for heating and cooling
Temperature regulating unit
for heating and cooling
series 152
Product range
Code 152650
Temperature regulating unit for heating and cooling with pump UPS 25-60
Code 152651
Temperature regulating unit for heating and cooling with pump UPS 25-80
Code 151000
Room thermostat and indoor sensor
Technical specification
- Materials: - body:
- hydraulic seals:
- insulation shell:
- Mixing valve:
- Medium:
- Max percentage of glycol:
- Working temperature range:
- Max working pressure:
- By-pass regulating range:
- Thermometer scale:
- Primary and secondary circuit connections:
- Servomotor: electric supply:
rating:
cycle time:
torque:
- Grundfos pump:
cod. 152650
cod. 152651
- Max ambient relative humidity:
- Ambient temperature:
- Protection class:
Function
The temperature regulating unit is designed to guarantee the
correct contribution of heating energy required by the user, by
measuring the outside and room temperature values to regulate the
correct system flow temperature for either heating or cooling.
It is supplied complete with:
4-way mixing valve, servomotor, pump, flow temperature sensor,
outside temperature sensor, system temperature return sensor,
cooling surface humidity control sensor, temperature controller, flow
and return thermometers, unions for connecting to the primary and
secondary circuits, with preformed shell insulation.
The unit is designed for connection for remote data transmission.
This unit solves the problems of installation of regulating
components in modern small and medium-sized systems, due to its
compact size and ease of use.
The unit is factory set for use with underfloor heating systems.
Head available at regulating unit connections
grey cast iron GG19
H (m w.g.)
EPDM
6
PPM
5
4-way
4
water, glycol solutions
30%
3
5÷60°C
2
6 bar
1
0,05÷0,5 bar
0÷60°C
0
0
1" F with union
230V 50 Hz
10 VA
240 s
Power consumption
10 N·m
model UPS 25-60
Speed
model UPS 25-80
95%
0÷40°C
IP 42
UPS 25-60
code 152650
3
2
1
1
2
3
4
5
6
Q (m
3
/h)
P
n
I
(A)
(W)
(rpm)
3
0,45
100
1800
2
0,30
65
1100
1
0,17
35
700
CALEFFI
01088/03 GB
H (m w.g.)
6
UPS 25-80
code 152651
5
4
3
3
2
2
1
1
0
0
1
2
3
4
5
6
Q (m
3
/h)
P
n
I
Speed
(A)
(W)
(rpm)
3
1,13
250
2450
2
1,04
220
1500
1
0,69
140
1000