CALEFFI 161010 Руководство - Страница 8
Просмотреть онлайн или скачать pdf Руководство для Контроллер CALEFFI 161010. CALEFFI 161010 20 страниц. Heating controller
R4
= demand contact of the heat generator (potential-free extra-low voltage
relay). If the voltage at the contact used is higher than 30 V, use the
auxiliary terminals at the 230 V side for the mixer.
PWM 1
= R1 speed signal, profile selectable
Adjustment and balance values menu system 1
Factory
Range
setting
System
1
1, 2
Tset
40 °C
15 °C ... 90 °C
TFcalculated
Yes
Yes, No
TMin
No
Yes, No
TMin
25 °C
15 °C ... 40 °C
TMax
Yes
Yes, No
TMax
50 °C
30 °C ... 90 °C
tLimit
5 min
1 ... 30 min
Cooling
No
Yes, No
TCool
16 °C
5 °C ... 25 °C
Condensat.
Yes
Yes, No
Chiller on
No
Yes, No
Pressure
No
Yes, No
PMin
0.6 bar
0.2 ... 10.0 bar
tMixer
75 s
30 ... 240 s
Corr.tMixer
90 s
5 ... 300 s
tPLAY
4 s
1...15 s
Block. prot.
Yes
Yes, No
PWM
Heating
Heating, Solar
Slab drying
-
-
TStart
20 °C
10 °C ... 30 °C
TMax
45 °C
20 °C ... 60 °C
Rise
5 K
1 ... 10 K
Rise time
24 h
1 ... 24 h
tBacking
7 d
1 ... 20 d
8
Description
System selection
Set flow temperature
Heat demand-based set flow temperature
calculation option
Minimum temperature heating circuit option
Minimum temperature heating circuit
Maximum temperature heating circuit option
Maximum temperature heating circuit
Time for which the calculated set flow tem-
perature is to be used
Cooling option
Cooling temperature
Dew point switch (DPS) option
Cooling demand on option
Low pressure monitoring option
Switch-on threshold low pressure monitoring
Mixer runtime
Surplus mixer runtime when the mixer is
closing
Mixer control time for change of flow
direction
Blocking protection option
PWM profile PWM A
Slab drying submenu
Slab drying start temperature
Slab drying holding temperature
Slab drying rise value
Slab drying rise time
Slab drying holding time
Factory
Range
setting
Start
-
Start, Cancelled
Language
Italiano
Deutsch, English,
Francais, Italiano
Reset
No
Yes, No
Operation
-
0 ... 9999
Pump
-
0 ... 9999
Mixer open
-
0 ... 9999
Mixer closed
-
0 ... 9999
Backup heating -
0 ... 9999
Max. S1
-
max. 999.9 °C
Max. S2
-
max. 999.9 °C
Max. S3
-
max. 999.9 °C
Min. press.
-
0.0 ... 10.0 bar
Max. press.
-
0.0 ... 10.0 bar
Version
-
-
All relays
Auto
Auto, Off
Man. 1
Auto
On, Auto, Off
Man. 2,3
Auto
Mixer closed, Auto,
Mixer open, Off
Man. 4
Auto
On, Auto, Off
back
Description
Activation / Deactivation slab drying
Language selection
back to factory settings
Operating days of the controller (balance val-
ue, cannot be set back to zero)
Balance values, can be set back to zero (see
page 16)
Display of software version
Operating modes of all relays
Manual mode relay 1
Manual mode relay 2,3
Manual mode relay 4