Step 11: Pump Switch Quick Test
TEST PUMP OFF: When the actuator rod on the VertiMAC™ pump
switch is in the down position (deactivated), the pump should be off and
the green power LED should be the only LED illuminated on the Sump
Advisor™ alarm panel.
TEST PUMP ON: When the actuator rod on the VertiMAC™ pump
switch is in the up position (activated), the pump should be on and the
green pump run LED should be illuminated on the Sump Advisor™
alarm panel.
Step 12: Sensor/Alarm Panel Quick Test
TEST HIGH LEVEL ALARM OFF: When the VertiMAC™ pump switch
is activated, the pump should be on, the green pump run LED should
illuminate, and the pump run auxiliary dry contacts will activate on the
Sump Advisor™ alarm panel.
TEST HIGH LEVEL ALARM ON: When the VertiMAC™ pump switch
is activated and the water level rises activating the float on the Sump
Advisor™ sensor it will also activate the Sump Advisor™ alarm panel.
When the alarm panel is an alarm condition, the red high sump LED
should illuminate, the buzzer should annunciate, and the alarm auxiliary
dry contacts will activate. Pressing the alarm silence pushbutton will
silence the buzzer. When the alarm condition is cleared, the system will
automatically reset itself for the next alarm cycle.
Included with Product
▪ Sump Advisor™ 2-Zone alarm panel
▪ Sump Advisor™ sensor
(VertiMAC™ Pump Switch sold separately)
Sump Advisor
12
4
10
1
5
7
10
2-Zone Alarm Panel and Sensor - Features
™
15
14
2
3
6
12
9
8
Customer Support
Online
alderonind.com
Email
QR Code
Scan code for full product details
Specifications
Sump Advisor™ Alarm Panel
Primary Power:
Secondary Power:
Auxiliary Contacts:
Battery:
Buzzer:
Sensor Connection:
Enclosure:
Certifications:
Sump Advisor™ Sensor
Alarm Activation:
Switching Contacts:
Cable Type:
VertiMAC™ Pump Switch, VM-Series
Primary Power:
Electrical:
Cable Type:
Connection Types:
Pumping Range:
Operating Temp:
Certifications:
Note: The VertiMAC™ pump switch must be used with pumps that provide integral thermal
overload protection.
13
1
Power On LED - The green LED illuminates to indicate the alarm panel has power
15
2
High Sump LED - The red LED illuminates during a high level alarm condition
16
3
Pump Run LED - The green LED illuminates to indicate the pump is running
4
Alarm Buzzer - Annunciates during an alarm condition
17
Alarm Test Pushbutton - Press to test the alarm to ensure proper operation; the
5
buzzer should annunciate, high sump LED should illuminate, and auxiliary contacts
should activate
Alarm Silence Pushbutton - Press to silence the buzzer during an alarm condition;
6
the alarm LED remains illuminated until the alarm condition has been cleared and the
alarm panel will auto reset for the next alarm cycle
Terminal Block - Connect the Sump Advisor™ sensor to the alarm panel for local
7
high level alarm and pump run indication
Auxiliary Contacts - Interface with an external device including building automation
8
systems and phone dialers; the contacts (normally open) are rated 24VDC/24VAC,
50/60 Hz, and 100mA maximum
9
Battery Backup - 9VDC battery (not included) for backup during power outages
Panel Compartment - Wire connector for 9VDC battery (backup power), auxiliary dry
10
contacts, and access cover with break away tabs for routing wire
11
Power Supply (not shown) - 120VAC, 60 Hz, 5-foot power cord
Mounting Holes - Two mounting holes are included on the alarm panel enclosure to
12
securely fasten in the desired mounting location
13
Sensor Housing - Internal signaling components protected, waterproof sensor
14
Sensor Cable - The 3-conductor cable sends signal from the sensor to the alarm panel
15
Mounting Tabs - Secures the sensor to the top of the VertiMAC™ pump switch
16
Float Basket - Houses high level float and protects from obstructions
17
Float - Rises and lowers inside the float basket based on the liquid level
18
Locking Tabs (not shown) - Secures float basket to bottom of sensor housing
120VAC, 60 Hz, 5-foot power cord
Class 2, 9-11.1VDC, 500 Milliamps
Normally Open, Class 2, 24VDC / 24VAC,
50/60 Hz, 100 Milliamps maximum
Standard 9VDC
(not included)
103 dB @ 2 feet
9VDC, 200 Milliamps minimum
(signaling device)
Indoor, rated Type 1
CSA
(US and Canada)
Approximately 4.0"
above pump activation level
(inches)
3-wire, common, high, and pump run
24VDC, 100 Milliamps maximum
PVC, 22 gauge, and 3-conductor
(sold separately)
120VAC or 240VAC, 60 Hz
(voltage depends on model/part number)
13 Amps, 120VAC 0.5HP or 240VAC 1.0HP
SJTOW (UL/CSA), thermoplastic, 16 gauge,
2-conductor, flexible, and water/oil resistant
Bare Lead
Piggyback Plug
(120/240VAC)
1.5" - 6.0"
(inches)
0 - 140° F
CSA
(US and Canada)
(normally open)
(120VAC or 240VAC)