2.3 Hardware

Structure:
A solid heat sink with two sidewalls and a cover made
of metal form the equipment assembly.
The semiconductors are mounted on the heat sink and
electrically connected with the printed circuit board,
which is fastened on top of it.
The terminals are at the front side of the unit.
Installation:
The site of installation must be dry and free of dust.
Mounting:
Power module is designed for wall or rack mounting.
For optimal cooling a distance of approx. 200 mm
around the unit must be kept free.
Dismantling the cover:
Both system plugs X102 and X103 are to unbolt
and to remove.
Subsequently, unbolt the four screws on the cover.
Now the cover can be raised and removed from the
side of the connector.
Connectors: Cover removed
- Phoenix system plugs X102, X103
(CAN, ALARM)
- Screw connections M5 on printed
circuit board (Ie, Upwr)
- Screw connection M5 on front of
heat sink (Earth)
Printed circuit board mounted on the heat sink
1
ABB Switzerland Ltd
Wall mounting
¢ ¡ £ ¡
200 mm
Power ON
Excitation ON
Overcurrent
Overtemperature
Alarm
CAN
Cover
CAN
X102
remove connectors
-Ie
CAN
ALARM
X102
X103
1
Document number
3BHS200200 E80
Rack mounting
200 mm
UNITROL 1000
Power Module 40 A
ALARM
Ie
Upwr
-
+
L1
L2
L3
ALARM
X103
open screws
L1
+Ie
Lang.
en
154 mm
Upwr
L2
L3
Rev. ind.
Page
A