4.6. Aeraulic connections from the unit

We recommend using the following to connect the InspirAIR
- Flexible plastic ducting type Algaine D.200 with female connector RF D.150 (11093065)
+ RCC D160/200 (11098186) or galvanised or Alflex rigid ducts
When installing the internal heating coil, it is mandatory to use galvanised ducts
on the edges of the coil (see internal preheating coil instructions).
Use of sound attenuator
We recommend installing sound attenuators for the two push flows (located at the front
of the machine):
- Type Octa Ø160 with seal for the Top 300 units
- Type Octa Ø200 with seal for the Top 450 units
We recommend using a straight duct at least 50 cm long at product outlet preferably
to ensure an optimum sound level.
sound attenuators if possible. Elbows are inadvisable.

4.7. Electrical connections

Connect the unit to the connector under the cable tray by a lead connected directly to the installation's switchboard.
Power supply: 230 V AC single-phase.
Characteristics and installation conditions of the power lead (not supplied)
- Cable cross-section: 3 x 1.5 mm
- The earth wire must be longer than the others (the last one to be disconnected if traction occurs)
Stripping length: 10 mm
The installer must check every time that the wires are pushed correctly into the connector.
The installation will include:
- dual-pole circuit breaker
- circuit protection with 30 mA differential circuit breaker
Connection to the connection terminal block installed on the product. Comply with the connections and polarities marked on the connector.

4.8. Electronic connections

View of customer connections on the electronic board:
X1
X2
X3
L
N
A
B
IBus connection:
®
InspirAIR
ext. preheating
coil
11023225
The top product metal plate incorporates cable tie feedthroughs to fix the cables neatly.
®
Top 450:
The same applies upstream and downstream of
2
minimum (maximum 2.5 mm
2
if end piece insulated or 4 mm
X4
X5
X6
A
B +V USB +24V +
-
®
InspirAIR
Top
ext. post-heating
coil
11023487
2
)
Reference
X7
X8
X9-X12
AI0 AI1 AO0
C13 Bahia
Curve Elec Bus
11015490
20
Function
X1
Power supply 230 V
X2
Internal preheating relay control
X3
Customer Modbus connection
X4
HMI connection
X5
USB connection
X6
IBus connection
X7
Push button connection
X8
Dry contact/NO by default
Inlets-outlets 0-10 V
X9: Analogue input 0
X10: Analogue input 1
X9-X12
X11: Analogue output
X12:
Push button connection:
230 V
X7
Dry contact/NO by default
230 V
X8 X12
: