Figure 3: Combustion Air Roof Termination Locations
All inlet air ducts must be sealed air tight.
When using sealed combustion, the combustion air inlet and vent outlet must be located on
the same surface (same wall, roof, etc.). See Figures 4. This is required so that equal pressure
zones are acting on both the air inlet and vent outlet. This makes the installation a balanced
vent system, which helps maintain stable combustion characteristics.
Figure 4: Sealed Combustion Air Inlet and Vent Outlet Locations (Wall & Roof)