Step 2: Connect Switches to Input Terminals
To finish this quick-start exercise or study other examples in this manual, you'll need
to connect some input switches as shown below. For most models, the F1-04SIM
Input Simulator is a quick way to install four switches on inputs X0 -- X3. DC-powered
units will require routing DC power to the simulator as shown. We recommend using
one of the models compatible with the input simulator as you learn the DL105.
However, you may wire individual toggle switches to AC-powered units as shown, as
long as you follow the instructions in the accompanying WARNING note.
F1- -130DR/F1- -130DR- -CE,
F1- -130DD/F1- -130DD- -CE,
F1- -130DA
ON
FACTS
engineering
OFF
F1--04SIM
F1- -130AR, F1- -130AD, F1- -130AA
(AC input versions, 120VAC only)
Toggle Switches, UL Listed
(DC input versions)
Slide simulator under
left-most terminals
and tighten screws.
Getting Started
F1- -130DR- -D, F1- -130DD- -D
(DC-powered versions)
FACTS
engineering
F1--04SIM
WARNING: DO NOT wire the
toggle switches as shown to
240VAC-powered
discrete inputs will only accept
120VAC nominal. Also, remove
power and unplug the DL105
when wiring the switches. Only
use UL-approved switches rated
for at least 250VAC, 1A. Firmly
mount
the
switches
using.
NEVER use the input simulator
on these units with AC-type
discrete inputs.