Armstrong AGEplus Series Инструкции по установке и эксплуатации - Страница 2

Просмотреть онлайн или скачать pdf Инструкции по установке и эксплуатации для Система водоснабжения Armstrong AGEplus Series. Armstrong AGEplus Series 2 страницы.

• Controlled to follow constant speed for systems with constant demand (1-4).
Setting is done via the rotating button on the top of the terminal box.
Electronic controlled settings
Normal setting, to cover app. 90 % of
all installations.
Factory-setting
Reduced differential pressure. For
systems with little resistance.
Increased differential pressure. For
systems with high resistance as
radiant floor heating systems.
Fixed speed settings
1-4 speeds1. For small
systems and 4. for large
systems or venting
GENERAL
In all AGEplus circulators, Pressure Loss Compensation (P.L.C.) is included
in the control, which means that the circulator does not follow a constant
differential pressure but takes into account the decreasing pressure needs
at decreasing flow. This setting is in the auto controlling mode. See Fig. 7.
3
Fig. 7
2
1
3
2
1
SIGNALS
AGEplus circulators have two LED's on the terminal box for status indica-
tion. Power to the circulator is indicated with the green LED. The red LED
will be on if the circulator detect a fault. Reset is carried out by switching
the mains supply off for 5 sec. and then on again. See Fig. 8.
Signal LED
No light
Green light
Red light
ERROR SIGNALS
The red light on the back of the terminal box will, in case of an error, indicate
the type of error detected by the electronic. Approximately every minute the
light will blink a number of times.
Number of blinks
Error
1
Overheating of the electronics
2
Motor overheated
3
Power overload
4
Current overload
5
Speed error
6
Under or over voltage
S. A. Armstrong Limited
Armstrong Integrated Limited
23 Bertrand Avenue
Wenlock Way
Toronto, Ontario
Manchester
Canada, M1L 2P3
United Kingdom, M12 5JL
T: 416-755-2291
T: +44 (0) 8444 145 145
F: 416-759-9101
F: +44 (0) 8444 145 146
For Armstrong locations worldwide, please visit www.armstrongintegrated.com
Auto controlled
performance for
power savings
and extra comfort
where flow
demands are
changing.
Fixed speed for systems with
constant resistance and radi-
ant floor heating systems.
4
Fig. 8
4
Red = Alam
Green = Power on
Description
Main supply switched off
Normal operation – power on
Error detected by the electronics
ERROR RELAY
The AGEplus has a fault relay. The relay
has both a NC and a NO connecting. See
Fig. 9.
FAULT FINDING
Fault
Cause
The circulator is not
See under heading
running.
"Signals"
Circulator will not start /
Impurities in the
is running irregularly.
circulator.
The circulator is running
Air in the system.
but no flow.
Closed valve
Circulator speed too
Circulator noisy.
high. Static head too
low. Air in system
SERVICE / MAINTENANCE
Armstrong's AGEplus Series range of glandless circulators is virtually
maintenance free and in a well designed system should give many years of
trouble free operation.
If motor shaft is seized as a result of a long period without use or due to
accumulation of impurities, it should be freed. Insert a screwdriver through
the venting plughole and into the slot in the end of the shaft and rotate.
Please note: Any repairs required to the internal electrical parts of the circu-
lator, are to be carried out by an Armstrong approved service organisation.
Transport, Handling and Storage Instructions
a. Transport.
i . AGEplus circulators are despatched fully assembled. AGEplus
circulators are packed for transport by mornal road, sea and air
carriers.
b. Handling
i. Crushing Hazard.
Ii. When lifting an AGEplus circulator above a weight of 25
kg, use lifting equipment haveing a safe working load
rating suitable for the load specified. Use suitable slings
for lifting any circulator..
c. Storage
i. Short term Storage (six weeks). If the AGEplus circulator is not to
be installed immediately after unpacking, then it is to be be stored
in a cool dry dust free location.
Ii. Long term storage. If the AGEplus circulator is not to be installed
for period of longer than six weeks after receipt on site, then it is
to be retained in its packing case. If the casing case is disposed
of, then the inlet and outlet connections are to be blanked off with
suitable clean covers to prevent ingress of damaging solids.
DECLARATION OF CONFORMITY
Armstrong hereby declares that this unit complies with the following
relevant provisions
i. EC Machinery Directives 89/392/EEC, 91/368/EEC, 93/44/EEC,
93/68/EEC
Ii. Electromagnatic compatability standard 89/336/EEC, 02/31/EEC,
93/68/EEC
iii. Applied harmonisation of standards EN809, EN50 081-1,
EN50 082-1, EN50-081-2, EN50-082-2.
Fig. 9
Action
Reset fault indication.
Check main supply and fuses.
See under heading
"Service/ Maintenance".
Vent circulator and
system.Open valve.
Decrease set point of
control. Increase inlet
pressure. Vent circulator
and system.
© S.A. Armstrong Limited 2011