Condensate Neutralization Tank User Instructions
INTRODUCTION
The Condensate Neutralization Tank is used for neutralizing condensate from condensing boilers
that use natural gas or propane as fuel. Waste condensate, produced by the burning of these
fuels, is potentially harmful to the environment and can corrode unprotected piping systems. The
kit is used to neutralize the acidic PH of the condensate to ensure the harmful effects are
minimized.
Features and Benefits:
Prevents acidic condensate from corroding pipes and sewer systems.
Environmentally friendly.
Fast and easy installation.
Kit materials are made from corrosion resistant materials.
For use on all types of Natural Gas and Propane appliances.
Initial charge of neutralizer agent is included.
Includes: baffles designed to channel flow thoroughly for complete neutralization, integral
bypass to prevent condensate backflow into appliance, NPT connections with unions for fast
and versatile installation.

INSTALLATION INSTRUCTIONS

NOTE: Check with your local water authority for regulations regarding discharge of treated
condensate into a drain or sewer system.
W A R N I N G !
RISK OF DAMAGE TO APPLIANCE!
Follow these instructions carefully to avoid damage to equipment and appliances.
The Condensate Neutralization Tank can be installed using either of the following methods:
• Neutralization tank is installed such that the inlet and discharge of the tank are at a lower
elevation than the AERCO condensate trap outlet. This can be achieved by:
a) Installing the Neutralization Tank in a pit (see Figure 2).
b) Elevating the AERCO boiler/water heater(s) and the AERCO condensate trap(s) (see
Figure 3).
• A condensate pump is used to lift the condensate from the appliance to the Neutralization
Tank (Figure 4).
Do not allow exhaust flue gases to vent through the Neutralization Tank. Flue gas leakage can
cause injury or death from carbon monoxide. Ensure the AERCO condensate trap is properly
installed with the boiler/water heater, upstream of the Neutralization Tank. See the boiler/water
heater installation manual for condensate trap installation instructions.
Connection to the appliance and Neutralization Tank must be installed to ensure that no
condensate backflow into the appliance can occur.
TID-0074_0H
8/22/2022
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Page 2 of 14