Acorn Safety SOA50-RH Инструкции по установке, эксплуатации и техническому обслуживанию - Страница 4

Просмотреть онлайн или скачать pdf Инструкции по установке, эксплуатации и техническому обслуживанию для Сантехническая продукция Acorn Safety SOA50-RH. Acorn Safety SOA50-RH 6 страниц.

Installation & Operation Manual

INSTALLATION INSTRUCTIONS:

Supplies required: (not provided by Acorn )
1. Wall/deck mounting hardware to install assembly.
2. Wall fasteners for sign mounting.
3. Pipe sealant or Teflon tape for sealing water
connections.
IMPORTANT: FLUSH WATER SUPPLY LINES PRIOR
TO CONNECTION TO SAFETY EQUIPMENT.
Notes:
Top of spray nozzles must be between 33"- 45' from
finished floor in order to meet ANSI Z358.1
Refer to Rough-in for location of supply and drain lines.
Fragments of Teflon tape or pipe sealant residue can
interfere with the proper operation of this unit. Ensure
pipe sealant methods do not cause contamination in
the system.
STEP ONE: MOUNTING
1. Mark desired location on counter top and drill a 1.375"
Dia. hole to accept swing arm assembly. Leave space
between backs plash and/or wall for swing arm
assembly to rotate 90 degrees without obstruction.
2. Place swing arm assembly into drilled hole and
secure with supplied washer and nut to hold unit in
place.
3. Assemble strainer to inlet of fitting with close nipple
provided.
STEP TWO: SUPPLY LINE
1. Install water line (supplied by others) in a position to
align with ½" strainer.
2. Open water supply.
3. Test for leaks, proper operation and flow.
STEP THREE: SIGNAGE & INSPECTION
1. Position sign with clear visibility, in close proximity to
safety equipment and mark mounting hole locations.
2. Select appropriate ¼" anchors, screws and washers
(Supplied by others) to install signage.
3. Attach inspection tag supplied, with plastic zip tie.
Acorn Safety
a division of Acorn Engineering Company™
Manual #7109-401-001
MOUNTING SCREWS
(PROVIDED BY
INSTALLER)
Page 4 of 6
1/2" MALE NPT
CONNECTION TO
WATER LINE
(SUPPLIED BY
INSTALLER)
Date: 05/17/13