Armstrong Air Conditioning 4SCU13LE Series Руководство по установке и обслуживанию - Страница 12

Просмотреть онлайн или скачать pdf Руководство по установке и обслуживанию для Кондиционер Armstrong Air Conditioning 4SCU13LE Series. Armstrong Air Conditioning 4SCU13LE Series 20 страниц. Split system air conditioner

Armstrong Air Conditioning 4SCU13LE Series Руководство по установке и обслуживанию
6. When 500 microns or lower is maintained, close the
manifold gauge valves, turn off the vacuum pump, and
disconnect the manifold gauge center port hose from
the vacuum pump. Attach the manifold gauge center
port hose to a nitrogen cylinder with pressure regulator
set to 150 psig and purge the hose. Open the manifold
gauge valves to break the vacuum in the line set and
indoor unit. Close the manifold gauge valves.
7. Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line
set and indoor unit until 500 microns is maintained
within a 20-minute period after shutting off the
vacuum pump and closing the manifold gauge valves.
9. When the requirements above have been met,
disconnect the manifold hose from the vacuum pump
and connect it to an upright cylinder of R410A refriger-
ant. Open the manifold gauge valves to break the
vacuum in the line set and indoor unit. Close manifold
gauge valves and shut off R410A cylinder and remove
manifold gauge set.
Page 12
# 48387H005