Aerco AM 1000 Технические инструкции - Страница 6
Просмотреть онлайн или скачать pdf Технические инструкции для Инструменты Aerco AM 1000. Aerco AM 1000 10 страниц. Thermal insulation replacement kit for am series models
AM Series Thermal Insulation Replacement Instruction
Replacing the Heat Exchanger's Thermal Insulation – Continued
4.
Align the bolt holes in the heat exchanger (detail B in Figure 8) with the corresponding
hole in the thermal insulation (detail A in Figure 8).
5.
Install the thermal insulation in the heat exchanger, holding it in place with the screw and
washer included with the kit (see Figure 9). ). It is recommended that you use a high
temperature anti-seize compound when installing the screw to facilitate removal during
subsequent maintenance.
Figure 8: Replace the Thermal Insulation
6. Replacing Burner's Thermal Insulation
The burner's thermal insulation must be checked every year and replaced if it is not intact.
Inspect for any damage including cracks, chips, or other damage, and replace if any damage is
found. These instructions will be repeated on each burner in the unit.
1.
Unscrew the screws holding the electrodes in place (see Figure 10).
2.
Remove both the ignition and flame detection electrodes (see Figure 11).
Figure 10: Remove Electrode's Screws
07/28/2014
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
Kit # 62632006
Replacing Burner's Thermal Insulation
Figure 9: Install the Thermal Insulation
Figure 11: Remove the Electrodes
TID-0120_0A