3 PRODUCT DESCRIPTION
3.1 GENERAL DESCRIPTION
The AMC-310 AirSense is a non-dispersive infrared analyzer for measuring environmental CO
concentration in ventilation systems and indoor living spaces. Its measurement range of
0 – 5000 ppm (parts per million; 1000 ppm = 0.1%) covers the range required to monitor
compliance with ASHRAE or other ventilation efficiency standards.
Packaged in a compact enclosure, the Model 310 can be discreetly installed anywhere from the
boardroom to the boiler room. Standard center wiring access and fully floating outputs make
installation a snap. The Model 310 provides several output alternatives. A voltage or 4 – 20 mA
current output is standard. An optional LCD readout is available. An optional relay contact can
be configured to open or close above a user-adjustable set point. A simple one-point calibration
procedure and a built-in calibration port that requires no special fittings or adapters make the
Model 310 simple to maintain.
3.1.1 ANALYZER DETAILS
OPERATING TEMPERATURE:
OPERATING PRESSURE:
HUMIDITY:
WARM-UP TIME:
CALIBRATION VERIFICATION:
SIGNAL OUTPUT:
SENSOR TYPE:
RESPONSE TIME:
ACCURACY:
REPEATABILITY:
TYPICAL DRIFT (per year):
LIFE EXPECTANCY:
Turn off power supply before removing or replacing the sensor/transmitter or sensor.
AMC-310 AirSense Infrared CO
0 to 50 ºC (32 to 122 ºF)
Ambient atmospheric pressure.
0 to 90% RH, non-condensing.
3 minutes.
10 minutes (typical).
4 – 20 mA or 0 – 12 volts DC.
Diffusion or sample draws non-dispersive infrared (NDIR).
Less than 1 minute.
±5% of reading or ±75 ppm, whichever is greater.
±20 ppm.
±75 ppm (@ 1200 ppm).
10 years (typical).
Analyzer
2
5
2